Chapter 12 Descriptions of Parameter SettingsMS300
 The parameters record when the fault occurs and forces a stop.
 When low-voltage at stop fault (LvS) occurs, the fault is not recorded. When low-voltage during
operation faults (LvA, Lvd, Lvn) occur, the faults are recorded.
 When dEb function is valid and enabled, the drive executes dEb and records fault code 62 to
 Pr.06-17–Pr.06-22 and Pr.14-70–Pr.14-73 simultaneously.
06-23
Fault Output Option 1
06-24
Fault Output Option 2
06-25
Fault Output Option 3
06-26
Fault Output Option 4
Settings
 Use these parameters with multi-function output terminal (set Pr.06-23–Pr.06-26 to 35–38) for
the specific requirement. When a fault occurs, the corresponding terminals are activated.
Convert the binary value to a decimal value before you enter the value for Pr.06-23–Pr.06-26.
0: No fault record
1: Over-current during acceleration (ocA)
2: Over-current during deceleration (ocd)
3: Over-current during steady operation (ocn)
4: Ground fault (GFF)
6: Over-current at stop (ocS)
7: Over-voltage during acceleration (ovA)
8: Over-voltage during deceleration (ovd)
9: Over-voltage during constant speed (ovn)
10: Over-voltage at stop (ovS)
11: Low-voltage during acceleration (LvA)
12: Low-voltage during deceleration (Lvd)
13: Low-voltage during constant speed (Lvn)
14: Low-voltage at stop (LvS)
15: Phase loss protection (orP)
16: IGBT over-heat (oH1)
18: IGBT temperature detection failure ( tH1o)
21: Drive over-load (oL)
22: Electronics thermal relay 1 protection
(EoL1)
23: Electronics thermal relay 2 protection
(EoL2)
24: Motor overheating PTC/ PT100 (oH3)
26: Over torque 1 (ot1)
0–65535 (refer to bit table for fault code)
Fault Code
bit 0
bit 1
bit 2
current Volt.
366
Default: 0
bit 3
bit 4
bit 5
OL
SYS FBK
EXI
bit 6
CE