Parameter Set-Up; Quick Menu Key Functions - Danfoss VLT AutomationDrive FC 301 Programming Manual

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

How to Program

2.1.5 Parameter Set-up

The frequency converter can be used for practically all
assignments and offers 2 programming mode options:
Main menu mode.
Quick menu mode.
Main menu provides access to all parameters. Quick menu
takes the user through a few parameters, making it
possible to start operating the frequency converter.
Change a parameter in either main menu mode or quick
menu mode.

2.1.6 Quick Menu Key Functions

Press [Quick Menu] to enter a list of different areas
contained in the Quick Menu.
Select Q1 My Personal Menu to show the selected personal
parameters. These parameters are selected in
parameter 0-25 My Personal Menu. Up to 50 different
parameters can be added in this menu.
0RPM
Quick Menus
Q1 My Personal Menu
Q2 Quick Setup
Q4 Smart Setup
Q5 Changes Made
Illustration 2.13 Quick Menus
Select Q2 Quick Setup to go through a selection of
parameters to get the motor running almost optimally. The
default settings for the other parameters consider the
required control functions and the configuration of signal
inputs/outputs (control terminals).
The parameter selection is effected with the navigation
keys. The parameters in Table 2.2 are accessible.
M0013101
Programming Guide
0.00A
1(1)
Danfoss A/S © 10/2019 All rights reserved.
Parameter
Parameter 0-01 Language
Parameter 1-20 Motor Power [kW]
Parameter 1-22 Motor Voltage
Parameter 1-23 Motor Frequency
Parameter 1-24 Motor Current
Parameter 1-25 Motor Nominal Speed
Parameter 5-12 Terminal 27 Digital Input
Parameter 1-29 Automatic Motor
Adaptation (AMA)
Parameter 3-02 Minimum Reference
Parameter 3-03 Maximum Reference
Parameter 3-41 Ramp 1 Ramp Up Time
Parameter 3-42 Ramp 1 Ramp Down Time
Parameter 3-13 Reference Site
Table 2.2 Selection of Parameter
1) If terminal 27 is set to [0] No operation, no connection to +24 V
on terminal 27 is necessary.
Select Changes made to get information about:
The last 10 changes. Use the [
keys to scroll between the last 10 changed
parameters.
The changes made since default setting.
Select Loggings to get information about the show line
readouts. The information is shown as graphs.
Only parameters selected in parameter 0-20 Display Line 1.1
Small and parameter 0-24 Display Line 3 Large can be
viewed. It is possible to store up to 120 samples in the
memory for later reference.
Setting
2
[kW]
[V]
[Hz]
[A]
[RPM]
1)
[0] No function
[1] Enable complete
AMA
[RPM]
[RPM]
[s]
[s]
] [
] navigation
17
2