Parameter Descriptions
5-40 Function Relay
Option:
Function:
[7]
Run in
The motor runs within the
range/no warn
programmed current and the speed
ranges set in
parameter 4-50 Warning Current Low
and parameter 4-53 Warning Speed
High. No warnings.
[8]
Run on ref/no
The motor runs at reference speed.
warn
No warnings.
[9]
Alarm
An alarm activates the output. No
warnings.
[10]
Alarm or
An alarm or a warning activates the
warning
output.
[11]
At torque limit The torque limit set in
parameter 4-16 Torque Limit Motor
Mode or parameter 4-17 Torque Limit
Generator Mode has been exceeded.
[12]
Out of current
The motor current is outside the
range
range set in parameter 4-18 Current
Limit.
[13]
Below current,
The motor current is lower than set
low
in parameter 4-50 Warning Current
Low.
[14]
Above current,
The motor current is higher than
high
set in parameter 4-51 Warning
Current High.
[15]
Out of speed
Output speed/frequency is outside
range
the frequency range set in
parameter 4-52 Warning Speed Low
and parameter 4-53 Warning Speed
High.
[16]
Below speed,
Output speed is lower than the
low
setting in parameter 4-52 Warning
Speed Low.
[17]
Above speed,
Output speed is higher than the
high
setting in parameter 4-53 Warning
Speed High.
[18]
Out of feedb.
Feedback is outside the range set
range
in parameter 4-56 Warning Feedback
Low and parameter 4-57 Warning
Feedback High.
[19]
Below
Feedback is below the limit set in
feedback, low
parameter 4-56 Warning Feedback
Low.
[20]
Above
Feedback is above the limit set in
feedback, high
parameter 4-57 Warning Feedback
High.
[21]
Thermal
Thermal warning turns on when the
warning
temperature exceeds the limit
either in motor, frequency
M0013101
Programming Guide
5-40 Function Relay
Option:
[22]
[23]
[24]
[25]
[26]
[27]
[28]
[29]
[30]
[31]
[32]
Danfoss A/S © 10/2019 All rights reserved.
Function:
converter, brake resistor, or
connected thermistor.
Ready,no
The frequency converter is ready for
thermal W
operation and there is no overtem-
perature warning.
Remote,ready,
The frequency converter is ready for
no TW
operation and is in auto-on mode.
There is no overtemperature
warning.
Ready, Voltage
The frequency converter is ready for
OK
operation and the mains voltage is
within the specified voltage range
(see the General Specifications
section in the design guide).
Reverse
The motor runs (or is ready to run)
clockwise when logic = 0 and
counterclockwise when logic = 1.
The output changes as soon as the
reversing signal is applied.
Bus OK
Active communication (no timeout)
via the serial communication port.
Torque limit &
Use for performing a coasted stop
stop
in a torque limit condition. If the
frequency converter has received a
stop signal and is in torque limit,
the signal is logic 0.
Brake, no
Brake is active and there are no
brake war
warnings.
Brake ready,
Brake is ready for operation and
no fault
there are no faults.
Brake fault
Output is logic 1 when the brake
(IGBT)
IGBT is short-circuited. Use this
function to protect the frequency
converter if there is a fault on the
brake module. Use the digital
output/relay to cut out the main
voltage from the frequency
converter.
Relay 123
Digital output/relay is activated
when [0] Control Word is selected in
parameter group 8-** Comm. and
Options.
Mech brake
Selection of mechanical brake
ctrl
control. When selected parameters
in parameter group 2-2* Mechanical
Brake are active. The output must
be reinforced to carry the current
for the coil in the brake. Usually
solved by connecting an external
relay to the selected digital output.
3
3
151