Parameter Descriptions
5-18 Terminal X30/4 Digital Input
Option:
[94]
Light Load
Detection
[95]
Evacuation
3
3
mode
[96]
Mains Loss
[97]
Mains Loss
Inverse
[98]
Start edge
triggered
[100]
Safe Option
Reset
[106]
Set Master
Home
[107]
Target Inverse
[108]
Enable Mast.
Offset
[109]
Enable Vir.
Master
[110]
Start Homing
[111]
Activate Touch
[112]
Relative
Position
[113]
Enable
Reference
[114]
Sync. to Pos.
Mode
[115]
Home Sensor
[116]
Home Sensor
Inv.
[117]
Touch Sensor
[118]
Touch Sensor
Inv.
[119]
Speed Mode
[122]
Position Vir.
Master
[123]
Master Marker
[124]
Master Marker
Inv.
[125]
Follower
Marker
[126]
Follow. Marker
Inv.
[231]
Power Limit
Mot.
[232]
Power Limit
Gen.
[233]
Power Limit
Both
[234]
Light Load
+Evacuation
132
®
VLT
AutomationDrive FC 301/302
Function:
Danfoss A/S © 10/2019 All rights reserved.
5-19 Terminal 37 Safe Stop
Use this parameter to configure the Safe Torque Off functionality.
A warning message makes the frequency converter coast the
motor and enables the automatic restart. An alarm message
makes the frequency converter coast the motor and requires a
manual restart (via a fieldbus, Digital I/O, or by pressing [RESET]
®
on the LCP). When the VLT
PTC Thermistor Card MCB 112 is
mounted, configure the PTC options to get the full benefit from
the alarm handling.
Option:
Function:
[1]
Safe Stop
Coasts the frequency converter
Alarm
when Safe Torque Off is activated.
Manual reset from LCP, digital input,
or fieldbus.
[3]
Safe Stop
Coasts the frequency converter
Warning
when Safe Torque Off is activated
(terminal 37 off). When the Safe
Torque Off circuit is re-established,
the frequency converter continues
without manual reset.
[4]
PTC 1 Alarm
Coasts the frequency converter
when Safe Torque Off is activated.
Manual reset from LCP, digital input,
or fieldbus.
[5]
PTC 1 Warning Coasts the frequency converter
when Safe Torque Off is activated
(terminal 37 off). When the Safe
Torque Off circuit is re-established,
the frequency converter continues
without manual reset, unless a
digital input set to [80] PTC Card 1
is still enabled.
[6]
PTC 1 & Relay
This option is used when the VLT
A
PTC Thermistor Card MCB 112 gates
with a stop key through a safety
relay to terminal 37. Coasts the
frequency converter when Safe
Torque Off is activated. Manual
reset from LCP, digital input, or
fieldbus.
[7]
PTC 1 & Relay
This option is used when the VLT
W
PTC Thermistor Card MCB 112 gates
with a stop key through a safety
relay to terminal 37. Coasts the
frequency converter when Safe
Torque Off is activated (terminal 37
off). When the Safe Torque Off
circuit is re-established, the
frequency converter continues
without manual reset, unless a
digital input set to [80] PTC Card 1
is still enabled.
[8]
PTC 1 & Relay
This option enables using a
A/W
combination of alarm and warning.
®
®
M0013101