Troubleshooting
WARNING/ALARM 35, Option fault
An option alarm is received. The alarm is option-specific.
The most likely cause is a power-up or a communication
fault.
WARNING/ALARM 36, Mains failure
This warning/alarm is only active if the supply voltage to
the drive is lost and parameter 14-10 Mains Failure is not
set to [0] No function.
Troubleshooting
Check the fuses to the drive and mains supply to
the unit.
ALARM 37, Phase imbalance
There is a current imbalance between the power units.
6
6
ALARM 38, Internal fault
When an internal fault occurs, a code number defined in
Table 6.5 is shown.
Troubleshooting
Cycle power.
Check that the option is properly installed.
Check for loose or missing wiring.
It may be necessary to contact the Danfoss supplier or
service department. Note the code number for further
troubleshooting directions.
Number
Text
0
The serial port cannot be initialized. Contact the
Danfoss supplier or Danfoss service department.
256–258
The power EEPROM data is defective or too old.
Replace the power card.
512–519
Internal fault. Contact the Danfoss supplier or
Danfoss service department.
783
Parameter value outside of minimum/maximum
limits.
1024–1284
Internal fault. Contact the Danfoss supplier or
Danfoss service department.
1299
The option software in slot A is too old.
1300
The option software in slot B is too old.
1302
The option software in slot C1 is too old.
1315
The option software in slot A is not supported/
allowed.
1316
The option software in slot B is not supported/
allowed.
1318
The option software in slot C1 is not supported/
allowed.
1379–2819
Internal fault. Contact the Danfoss supplier or
Danfoss service department.
1792
Hardware reset of digital signal processor.
1793
Motor-derived parameters not transferred correctly
to the digital signal processor.
1794
Power data not transferred correctly at power-up
to the digital signal processor.
360
®
VLT
AutomationDrive FC 301/302
Number
1795
1796
1798
2561
2820
2821
2822
3072–5122
5123
5124
5125
5126
5376–6231
Table 6.5 Internal Fault Codes
ALARM 39, Heat sink sensor
No feedback from the heat sink temperature sensor.
The signal from the IGBT thermal sensor is not available on
the power card. The problem could be on the power card,
on the gatedrive card, or the ribbon cable between the
power card and gatedrive card.
WARNING 40, Overload of digital output terminal 27
Check the load connected to terminal 27 or remove the
short-circuit connection. Check parameter 5-00 Digital I/O
Mode and parameter 5-01 Terminal 27 Mode.
WARNING 41, Overload of digital output terminal 29
Check the load connected to terminal 29 or remove the
short-circuit connection. Also check parameter 5-00 Digital
I/O Mode and parameter 5-02 Terminal 29 Mode.
WARNING 42, Overload of digital output on X30/6 or
overload of digital output on X30/7
For terminal X30/6, check the load connected to terminal
X30/6 or remove the short-circuit connection. Also check
parameter 5-32 Term X30/6 Digi Out (MCB 101) (VLT
General Purpose I/O MCB 101).
For terminal X30/7, check the load connected to terminal
X30/7 or remove the short-circuit connection. Check
parameter 5-33 Term X30/7 Digi Out (MCB 101) (VLT
General Purpose I/O MCB 101).
Danfoss A/S © 10/2019 All rights reserved.
Text
The digital signal processor has received too many
unknown SPI telegrams. The AC drive also uses
this fault code if the MCO does not power up
correctly. This situation can occur due to poor EMC
protection or improper grounding.
RAM copy error.
Software version 48.3X or newer is used with MK1
control card. Replace with MKII issue 8 control
card.
Replace the control card.
LCP stack overflow.
Serial port overflow.
USB port overflow.
Parameter value is outside its limits.
Option in slot A: Hardware incompatible with the
control board hardware.
Option in slot B: Hardware incompatible with the
control board hardware.
Option in slot C0: Hardware incompatible with the
control board hardware.
Option in slot C1: Hardware incompatible with the
control board hardware.
Internal fault. Contact the Danfoss supplier or
Danfoss service department.
®
®