Parameter Descriptions
[120] Local ref active
3
3
[121] Remote ref
active
[122] No alarm
[123] Start command
activ
[124] Running reverse Output is high when the frequency
[125] Drive in hand
mode
[126] Drive in auto
mode
[151] ATEX ETR cur.
alarm
[152] ATEX ETR freq.
alarm
[153] ATEX ETR cur.
warning
144
®
VLT
AutomationDrive FC 301/302
Output is high when parameter 3-13
Reference Site = [2] Local.
Reference site set
Local
in parameter 3-13
reference
Reference Site
active
[120]
Reference site:
1
Local parameter
3-13 Reference Site
[2] Local
Reference site:
0
Remote parameter
3-13 Reference Site
[1] Remote
Reference site:
Linked to Hand/
Auto
Hand
1
Hand⇒off
1
Auto⇒off
0
Auto
0
Table 3.22 Local Reference Active
Output is high when
parameter 3-13 Reference Site = [1] Remote or
[0] Linked to hand/auto while the LCP is in
auto-on mode. See Table 3.22
Output is high when no alarm is present.
Output is high when there is an active start
command (that is via digital input bus
connection, hand-on, or auto-on), and no
stop or start command is active.
converter runs counterclockwise (the logical
product of the status bits running AND
reverse).
Output is high when the frequency
converter is in hand-on mode (as indicated
by the LED light above [Hand On]).
Output is high when the frequency
converter is in auto-on mode (as indicated
by the LED light above [Auto On]).
Selectable if parameter 1-90 Motor Thermal
Protection is set to [20] ATEX ETR or [21]
Advanced ETR. If Alarm 164 ATEX ETR
cur.lim.alarm is active, the output is 1.
Selectable if parameter 1-90 Motor Thermal
Protection is set to [20] ATEX ETR or [21]
Advanced ETR. If Alarm 166 ATEX ETR
freq.lim.alarm is active, the output is 1.
Danfoss A/S © 10/2019 All rights reserved.
[154] ATEX ETR freq.
warning
Remote
reference
[180] Clock Fault
active
[181] Prev.
[121]
Maintenance
0
[188] AHF Capacitor
Connect
1
[189] External Fan
Control
0
[190] Safe Function
0
active
0
[191] Safe Opt. Reset
req.
1
[192] RS Flipflop 0
[193] RS Flipflop 1
[194] RS Flipflop 2
[195] RS Flipflop 3
[196] RS Flipflop 4
[197] RS Flipflop 5
[198] RS Flipflop 6
[199] RS Flipflop 7
[221] IGBT-cooling
[222] Homing OK
[223] On Target
Selectable if parameter 1-90 Motor Thermal
Protection is set to [20] ATEX ETR or [21]
Advanced ETR. If Warning 165, ATEX ETR
freq.lim.warning is active, the output is 1.
The capacitors are turned on at 20%
(hysteresis of 50% gives an interval of 10–
30%). The capacitors are disconnected below
10%. The off delay is 10 s and restarts if the
nominal power goes above 10% during the
delay. Parameter 5-80 AHF Cap Reconnect
Delay is used to guarantee a minimum off-
time for the capacitors.
The internal logics for the internal fan
control is transferred to this output to make
it possible to control an external fan
(relevant for hp duct cooling).
See parameter group 13-1* Comparators.
See parameter group 13-1* Comparators.
See parameter group 13-1* Comparators.
See parameter group 13-1* Comparators.
See parameter group 13-1* Comparators.
See parameter group 13-1* Comparators.
See parameter group 13-1* Comparators.
See parameter group 13-1* Comparators.
Use this option for handling the overcurrent
trips. When the frequency converter detects
an overcurrent condition, it shows alarm 13,
Overcurrent and triggers a reset. If the
overcurrent condition occurs the 3
a row, the frequency converter shows alarm
13, Overcurrent and initiates a 3-minute delay
before the next reset.
NOTICE
This option is available only with
software version 48.XX.
Homing is completed with the selected
homing function parameter 17-80 Homing
Function
NOTICE
This option is available only with
software version 48.XX.
Positioning is completed and the on-target
signal is sent when the actual position is
within parameter 3-05 On Reference Window
for the duration of parameter 3-09 On Target
Time and the actual speed does not exceed
parameter 3-05 On Reference Window.
M0013101