Parameters: 2-** Brakes - Danfoss VLT AutomationDrive FC 301 Programming Manual

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

Parameter Descriptions

3.3 Parameters: 2-** Brakes

3.3.1 2-0* DC brakes
Parameter group for configuring the DC brake and DC hold
functions.
2-00 DC Hold Current
Range:
Function:
NOTICE
50 %
[ 0 - 160 %]
*
The maximum value depends
on the rated motor current.
Avoid 100% current for too
long. It may damage the
motor.
In VVC
values (<20%) of DC hold may
result in wrong currents with
larger motor sizes (>90 kW)
and should be avoided. In
cases when low DC hold
currents with larger motors is
required, select Flux control
core to ensure the right
currents.
Enter a value for holding current as
a percentage of the rated motor
current I
parameter 1-24 Motor Current. 100%
DC hold current corresponds to I
This parameter holds the motor
function (holding torque) or
preheats the motor.
This parameter is active if DC hold
is selected in parameter 1-72 Start
Function [0] or
parameter 1-80 Function at Stop [1].
2-01 DC Brake Current
Range:
Function:
NOTICE
50 %
[ 0 - 1000 %]
*
The maximum value depends
on the rated motor current.
Avoid 100% current for too
long. It may damage the
motor.
Enter a value for current as a
percentage of the rated motor
current I
parameter 1-24 Motor Current. 100%
DC brake current corresponds to
I
M,N
DC brake current is applied on a
stop command, when the speed is
M0013101
Programming Guide
+
control core, low
set in
M,N
.
M,N
, see
M,N
.
Danfoss A/S © 10/2019 All rights reserved.
2-01 DC Brake Current
Range:
Function:
lower than the limit set in
parameter 2-03 DC Brake Cut In
Speed [RPM]; when the DC Brake
Inverse function is active, or via the
serial communication port. The
braking current is active during the
time period set in
parameter 2-02 DC Braking Time.
2-02 DC Braking Time
Range:
Function:
10 s
[0 - 60 s]
Set the duration of the DC brake
*
current set in parameter 2-01 DC
Brake Current, once activated.
2-03 DC Brake Cut In Speed [RPM]
Range:
Function:
Size
[ 0 - par. 4-13
Set the DC brake cut-in speed for
related
RPM]
activation of the DC brake current
*
set in parameter 2-01 DC Brake
Current, upon a stop command.
2-04 DC Brake Cut In Speed [Hz]
Range:
Function:
NOTICE
Size
[ 0 - par. 4-14
related
Hz]
*
Parameter 2-04 DC Brake Cut In
Speed [Hz] is not effective
when parameter 1-10 Motor
Construction = [1] PM, non-
salient SPM.
Set the DC brake cut-in speed for
activation of the DC brake current
set in parameter 2-01 DC Brake
Current after a stop command.
2-05 Maximum Reference
Range:
Function:
Size
[ par. 3-02 -
This is an access parameter to
related
999999.999
parameter 3-03 Maximum Reference
*
Reference-
for legacy products. The maximum
FeedbackUnit]
reference is the highest value
obtainable by summing all
references. The maximum reference
unit matches the option selected in
parameter 1-00 Configuration Mode
and the unit in
parameter 3-01 Reference/Feedback
Unit.
3
3
79