Parameter Descriptions
13-01 Start Event
Select the boolean (true or false) input to activate smart logic
control.
Option:
[0]
False
3
3
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current
range
[8]
Below I low
[9]
Above I high
[10]
Out of speed
range
[11]
Below speed
low
[12]
Above speed
high
[13]
Out of feedb.
range
[14]
Below feedb.
low
202
®
VLT
AutomationDrive FC 301/302
Function:
Select the boolean (true or false)
input to activate smart logic
control.
Enters the fixed value - false.
Enters the fixed value - true.
The motor runs.
The motor runs within the
programmed current and speed
ranges set in
parameter 4-50 Warning Current Low
to parameter 4-53 Warning Speed
High.
The motor runs on reference.
The torque limit set in
parameter 4-16 Torque Limit Motor
Mode or parameter 4-17 Torque Limit
Generator Mode is exceeded.
The motor current limit set in
parameter 4-18 Current Limit is
exceeded.
The motor current is outside the
range set in parameter 4-18 Current
Limit.
The motor current is lower than set
in parameter 4-50 Warning Current
Low.
The motor current is higher than
set in parameter 4-51 Warning
Current High.
The speed is outside the range set
in parameter 4-52 Warning Speed
Low and parameter 4-53 Warning
Speed High.
The output speed is lower than the
setting in parameter 4-52 Warning
Speed Low.
The output speed is higher than
the setting in
parameter 4-53 Warning Speed High.
The feedback is outside the range
set in parameter 4-56 Warning
Feedback Low and
parameter 4-57 Warning Feedback
High.
The feedback is below the limit set
in parameter 4-56 Warning Feedback
Low.
Danfoss A/S © 10/2019 All rights reserved.
13-01 Start Event
Select the boolean (true or false) input to activate smart logic
control.
Option:
Function:
[15]
Above feedb.
The feedback is above the limit set
high
in parameter 4-57 Warning Feedback
High.
[16]
Thermal
The thermal warning turns on when
warning
the temperature exceeds the limit
in the motor, the frequency
converter, the brake resistor, or the
thermistor.
[17]
Mains out of
The mains voltage is outside the
range
specified voltage range.
[18]
Reversing
The output is high when the
frequency converter is running
counterclockwise (the logical
product of the status bits running
AND reverse).
[19]
Warning
A warning is active.
[20]
Alarm (trip)
A (trip) alarm is active.
[21]
Alarm (trip
A (trip lock) alarm is active.
lock)
[22]
Comparator 0
Use the result of comparator 0.
[23]
Comparator 1
Use the result of comparator 1.
[24]
Comparator 2
Use the result of comparator 2.
[25]
Comparator 3
Use the result of comparator 3.
[26]
Logic rule 0
Use the result of logic rule 0.
[27]
Logic rule 1
Use the result of logic rule 1.
[28]
Logic rule 2
Use the result of logic rule 2.
[29]
Logic rule 3
Use the result of logic rule 3.
[33]
Digital input
Use the result of digital input 18.
DI18
[34]
Digital input
Use the result of digital input 19.
DI19
[35]
Digital input
Use the result of digital input 27.
DI27
[36]
Digital input
Use the result of digital input 29.
DI29
[37]
Digital input
Use the result of digital input 32.
DI32
[38]
Digital input
Use the result of digital input 33.
DI33
[39]
Start
A start command is issued. This is
command
the default option.
[40]
Drive stopped
A stop command (jog, stop, quick
stop, coast) is issued – and not
from the SLC itself.
[41]
Reset Trip
A reset is issued.