Parameter Descriptions
Feedback
Disturbed feedback signal
Lowpass lter
f
= 10 Hz
g
Feedback
Filtered feedback signal
Illustration 3.49 Feedback Signal
7-07 Speed PID Feedback Gear Ratio
Range:
Function:
1
[ 0.0001 -
The frequency converter multiplies
*
32.0000 ]
the speed feedback by this ratio.
M0013101
Programming Guide
Illustration 3.50 Speed PID Feedback Gear Ratio
7-08 Speed PID Feed Forward Factor
Range:
0.6
t (Sec.)
0 %
*
7-09 Speed PID Error Correction w/ Ramp
Range:
Size
related
0.6
t (Sec.)
Illustration 3.51 Speed Error between Ramp and Actual Speed
Danfoss A/S © 10/2019 All rights reserved.
Motor
Par 7-07=1.00
Function:
[0 - 500 %]
The reference signal bypasses the
speed controller by the amount
specified. This feature increases the
dynamic performance of the speed
control loop.
Function:
[10 - 100000
The speed error between ramp and
RPM]
actual speed is held up against the
*
setting in this parameter. If the
speed error exceeds this parameter
entry, the speed error is corrected
via ramping in a controlled way.
Motor
Speed
7-09
Torque
Limit
Motor
Speed
7-09
Torque
Limit
Ramp
Motor Speed
n1
n2
3
Par 7-07=n1/n2
Time
Time
177
3