Troubleshooting
Bit Hex
Dec
Alarm word
15 00008000
32768
AMA not OK
16 00010000
65536
Live zero error
(A2)
17 00020000
131072
Internal fault (A38) KTY error
18 00040000
262144
Brake overload
(A26)
19 00080000
524288
U phase loss (A30) ECB error
20 00100000
1048576
V phase loss (A31) Hoist
21 00200000
2097152
W phase Loss
(A32)
22 00400000
4194304
Fieldbus fault
(A34)
23 00800000
8388608
24 V supply low
(A47)
24 01000000
16777216
Mains failure (A36) Reserved
25 02000000
33554432
1.8 V supply low
(A48)
26 04000000
67108864
Brake resistor
(A25)
27 08000000 134217728 Brake IGBT (A27)
28 10000000 268435456 Option change
(A67)
29 20000000 536870912 Drive initialized
(A80)
30 40000000 1073741824 Safe stop (A68)
31 80000000 2147483648 Mech. brake low
(A63)
Table 6.3 Description of Alarm Word, Warning Word, and Extended Status Word
The alarm words, warning words and extended status words can be read out via a serial bus or optional fieldbus for
diagnostics. See also parameter 16-94 Ext. Status Word.
M0013101
Programming Guide
Alarm word 2
Warning word
Reserved
No motor (W3)
Reserved
Live zero error
(W2)
10 V low (W1)
Fans error
Brake overload
(W26)
Brake resistor
(W25)
Brake IGBT (W27)
mechanical
brake (A22)
Reserved
Speed limit (W49) Reserved
Reserved
Fieldbus fault
(W34)
Reserved
24 V supply Low
(W47)
Mains failure
(W36)
Current limit
Current limit
(A59)
(W59)
Motor rotating
Low temp (W66)
unexpectedly
(A122)
Reserved
Voltage limit
(W64)
Reserved
Encoder loss
(W90)
Encoder loss
Output freq. lim.
(A90)
(W62)
PTC thermistor
Safe stop (W68)
(A74)
Dangerous
Extended status
failure (A72)
word
Danfoss A/S © 10/2019 All rights reserved.
Warning
Extended
word 2
status word
Auto DC
OVC active
braking
AC brake
KTY warn
Password timelock
number of allowed password trials
exceeded - timelock active
Fans warn
Password protection
0-61 = ALL_NO_ACCESS OR
BUS_NO_ACCESS OR
BUS_READONLY
ECB warn
Reference high
reference >parameter 4-55 Warning
Reference High
Hoist
Reference low
mechanical
reference <parameter 4-54 Warning
brake (W22)
Reference Low
Local reference
reference site = REMOTE -> auto on
pressed & active
Reserved
Protection mode notification
Reserved
Unused
Reserved
Unused
Power Limit
Unused
Motor
Power Limit
Unused
Generator
Reserved
Unused
Reserved
Unused
BackEMF too
Unused
high
PTC thermi-
Unused
stor (W74)
6
6
355