Parameter Descriptions
6-00 Live Zero Timeout Time
Range:
Function:
for a time period longer than the
time set in parameter 6-00 Live Zero
Timeout Time, the function selected
in parameter 6-01 Live Zero Timeout
Function is activated.
6-01 Live Zero Timeout Function
Option:
Function:
Select the timeout function. If the
input signal on terminal 53 or 54 is
below 50% of the value in
for a time period defined in
parameter 6-00 Live Zero Timeout
Time, then the function set in
parameter 6-01 Live Zero Timeout
Function is activated.
If several timeouts occur simulta-
neously, the frequency converter
prioritizes the timeout functions as
follows:
[0]
Off
*
[1]
Freeze output
Frozen at the present value.
[2]
Stop
Overruled to stop.
[3]
Jogging
Overruled to jog speed.
[4]
Max. speed
Overruled to maximum speed.
[5]
Stop and trip
Overruled to stop with subsequent
trip.
[20]
Coast
[21]
Coast and trip
M0013101
Programming Guide
Parameter 6-20 Terminal 54
Low Voltage
Parameter 6-22 Terminal 54
Low Current
Parameter 6-10 Terminal 53
Low Voltage
Parameter 6-12 Terminal 53
Low Current
Parameter 6-20 Terminal 54
Low Voltage
Parameter 6-22 Terminal 54
Low Current
Parameter 6-01 Live Zero
Timeout Function.
Parameter 8-04 Control
Word Timeout Function.
Danfoss A/S © 10/2019 All rights reserved.
3.7.2 6-1* Analog Input 1
Parameters for configuring the scaling and limits for analog
input 1 (terminal 53).
Ref./Feedback
[RPM]
Par 6-xx
1500
'High Ref./
Feedb. Value'
1200
900
600
300
Par 6-xx
'Low Ref./
150
Feedb. Value'
Ex.
1 V
Par 6-xx
'Low Voltage'or
'Low Current'
Illustration 3.43 Analog Input 1
6-10 Terminal 53 Low Voltage
Range:
Function:
Size
[ -10.00 - par.
Enter the low voltage value. This
related
6-11 V]
analog input scaling value should
*
correspond to the minimum
reference value set in
parameter 6-14 Terminal 53 Low Ref./
Feedb. Value.
6-11 Terminal 53 High Voltage
Range:
Function:
10 V
[ par. 6-10 -
Enter the high voltage value. This
*
10 V]
analog input scaling value should
correspond to the high reference
feedback value set in
parameter 6-15 Terminal 53 High
Ref./Feedb. Value.
6-12 Terminal 53 Low Current
Range:
Function:
0.14 mA
[ 0 - par. 6-13
Enter the low current value. This
*
mA]
reference signal should correspond
to the minimum reference value,
set in parameter 3-02 Minimum
Reference. Set the value to exceed
2 mA to activate the live zero
timeout function in
parameter 6-01 Live Zero Timeout
Function.
6-13 Terminal 53 High Current
Range:
Function:
20 mA
[ par. 6-12 -
Enter the high current value
*
20 mA]
corresponding to the high
5 V
10 V
Par 6-xx
Analog input
'High Voltage'or
'High Current'
163
3
3