Parameter Descriptions
[50]
On Reference
Active when a VLT® Advanced Cascade
Controller MCO 102 or VLT® Motion Control
MCO 305 is connected. The output is
controlled from the option.
[51]
MCO controlled
Active when a VLT® Advanced Cascade
Controller MCO 102 or VLT® Motion Control
MCO 305 is connected. The output is
controlled from the option.
[54]
24V Encoder
Digital outputs 27 and 29 simulates a single-
Sim
signal HTL encoder. Select source for the
signal generation in parameter 5-78 Term
27/29 Encoder Sim.
NOTICE
Option [54] 24V Encoder Sim must be
selected in both
parameter 5-30 Terminal 27 Digital
Output and parameter 5-31 Terminal 29
Digital Output. This option is only
available for software version 48.XX.
[55]
Pulse output
[58]
Actual Position
[59]
Actual Position
4-20mA
[60]
Comparator 0
See parameter group 13-1* Comparators. If
comparator 0 is evaluated as true, the
output goes high. Otherwise, it is low.
[61]
Comparator 1
See parameter group 13-1* Comparators. If
Comparator 1 is evaluated as true, the
output goes high. Otherwise, it is low.
[62]
Comparator 2
See parameter group 13-1* Comparators. If
comparator 2 is evaluated as true, the
output goes high. Otherwise, it is low.
[63]
Comparator 3
See parameter group 13-1* Comparators. If
comparator 3 is evaluated as true, the
output goes high. Otherwise, it is low.
[64]
Comparator 4
See parameter group 13-1* Comparators. If
comparator 4 is evaluated as true, the
output goes high. Otherwise, it is low.
[65]
Comparator 5
See parameter group 13-1* Comparators. If
comparator 5 is evaluated as true, the
output goes high. Otherwise, it is low.
[70]
Logic rule 0
See parameter group 13-4* Logic Rules. If
logic rule 0 is evaluated as true, the output
goes high. Otherwise, it is low.
[71]
Logic rule 1
See parameter group 13-4* Logic Rules. If
logic rule 1 is evaluated as true, the output
goes high. Otherwise, it is low.
[72]
Logic rule 2
See parameter group 13-4* Logic Rules. If
logic rule 2 is evaluated as true, the output
goes high. Otherwise, it is low.
[73]
Logic rule 3
See parameter group 13-4* Logic Rules. If
logic rule 3 is evaluated as true, the output
goes high. Otherwise, it is low.
[74]
Logic rule 4
See parameter group 13-4* Logic Rules. If
logic rule 4 is evaluated as true, the output
goes high. Otherwise, it is low.
M0013101
Programming Guide
[75]
Logic rule 5
[80]
SL digital
output A
[81]
SL digital
output B
[82]
SL digital
output C
[83]
SL digital
output D
[84]
SL digital
output E
[85]
SL digital
output F
[90]
kWh counter
pulse
[96]
Reverse After
Ramp
[98]
Virtual Master
Dir.
Danfoss A/S © 10/2019 All rights reserved.
See parameter group 13-4* Logic Rules. If
logic rule 5 is evaluated as true, the output
goes high. Otherwise, it is low.
See parameter 13-52 SL Controller Action. The
output goes high whenever the smart logic
action [38] Set dig. out. A high is executed.
The output goes low whenever the smart
logic action [32] Set dig. out. A low is
executed.
See parameter 13-52 SL Controller Action. The
input goes high whenever the smart logic
action [39] Set dig . out. B highis executed.
The input goes low whenever the smart
logic action [33] Set dig. out. B low is
executed.
See parameter 13-52 SL Controller Action. The
input goes high whenever the smart logic
action [40] Set dig. out. C high is executed.
The input goes low whenever the smart
logic action [34] Set dig. out. C low is
executed.
See parameter 13-52 SL Controller Action. The
input goes high whenever the smart logic
action [41] Set dig. out. D high is executed.
The input goes low whenever the smart
logic action [35] Set dig. out. D low is
executed.
See parameter 13-52 SL Controller Action. The
input goes high whenever the smart logic
action [42] Set dig. out. E high is executed.
The input goes low whenever the smart
logic action [36] Set dig. out. E low is
executed.
See parameter 13-52 SL Controller Action. The
input goes high whenever the smart logic
action [43] Set dig. out. F high is executed.
The input goes low whenever the smart
logic action [37] Set dig. out. F low is
executed.
Sends a pulse (200 ms pulse width) to
output terminal whenever kWh counter
changes (parameter 15-02 kWh Counter).
NOTICE
This option is available only with
software version 48.XX.
Indicates if the direction of rotation should
be reversed. Depends on whether the speed
reference is positive or negative after the
ramp specified in parameter 16-48 Speed Ref.
After Ramp [RPM]
NOTICE
This option is available only with
software version 48.XX.
A virtual master signal that controls the
rotation direction of followers.
3
3
143