Parameter Descriptions
15-11 Logging Interval
Array [4]
Range:
Size
related
0.000 ]
*
3
3
15-12 Trigger Event
Select the trigger event. When the trigger event occurs, a
window is applied to freeze the log. The log then retains a
specified percentage of samples before the occurrence of the
trigger event (parameter 15-14 Samples Before Trigger).
Option:
[0]
False
*
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current
range
[8]
Below I low
[9]
Above I high
[10]
Out of speed
range
[11]
Below speed
low
[12]
Above speed
high
[13]
Out of feedb.
range
[14]
Below feedb.
low
[15]
Above feedb.
high
[16]
Thermal
warning
[17]
Mains out of
range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip
lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
244
Function:
[ 0.000 -
Enter the interval in ms between
each sampling of the variables to
be logged.
Function:
Danfoss A/S © 10/2019 All rights reserved.
®
VLT
AutomationDrive FC 301/302
15-12 Trigger Event
Select the trigger event. When the trigger event occurs, a
window is applied to freeze the log. The log then retains a
specified percentage of samples before the occurrence of the
trigger event (parameter 15-14 Samples Before Trigger).
Option:
[33]
[34]
[35]
[36]
[37]
[38]
[50]
[51]
[60]
[61]
15-13 Logging Mode
Option:
[0]
*
[1]
15-14 Samples Before Trigger
Range:
50
*
15-15 Info Message: "Service Log Full"
See Service log.
By enabling this parameter, a text message is shown in the drive
when the service log runs full: Clear logs, Service log full: 28
[M26]. The message recommends to clear the log.
Option:
[0]
*
[1]
Function:
Digital input
DI18
Digital input
DI19
Digital input
DI27
Digital input
DI29
Digital input
DI32
Digital input
DI33
Comparator 4
Comparator 5
Logic rule 4
Logic rule 5
Function:
Log always
Select [0] Log always for continuous
logging.
Log once on
Select [1] Log once on trigger to
trigger
start and stop logging conditionally
using parameter 15-12 Trigger Event
and parameter 15-14 Samples Before
Trigger.
Function:
[0 - 100 ]
Before a trigger event, enter the
percentage of all samples which
should be retained in the log. See
also parameter 15-12 Trigger Event
and parameter 15-13 Logging Mode.
Function:
Disabled
Enabled
Enable message
M0013101