Parameter Descriptions
Input) to [32] Pulse input. If terminal 29 is used as an input,
set parameter 5-01 Terminal 27 Mode to [0] Input.
Ref.
(RPM)
High
3
3
ref.
value
P 5-53/
p 5-58
Low
ref.
value
P 5-52/
p 5-57
Low freq.
P 5-50/
P 5-55
Illustration 3.39 Pulse Input
5-50 Term. 29 Low Frequency
Range:
100 Hz
*
Hz]
5-51 Term. 29 High Frequency
Range:
Size
related
Hz]
*
5-52 Term. 29 Low Ref./Feedb. Value
Range:
Size
related
- 999999.999
*
Reference-
FeedbackUnit]
5-53 Term. 29 High Ref./Feedb. Value
Range:
Size
related
- 999999.999
*
Reference-
FeedbackUnit]
156
High freq.
P 5-51/
P 5-56
Function:
[0 - 110000
Enter the low frequency limit
corresponding to the low motor
shaft speed (that is low reference
value) in parameter 5-52 Term. 29
Low Ref./Feedb. Value. Refer to
Illustration 3.39.
Function:
[0 - 110000
Enter the high frequency limit
corresponding to the high motor
shaft speed (that is high reference
value) in parameter 5-53 Term. 29
High Ref./Feedb. Value.
Function:
[-999999.999
Enter the low reference value limit
for the motor shaft speed [RPM].
This is also the lowest feedback
value, see also parameter 5-57 Term.
33 Low Ref./Feedb. Value. Set
terminal 29 to digital input
(parameter 5-02 Terminal 29 Mode =
[0] input (default) and
parameter 5-13 Terminal 29 Digital
Input = applicable value).
Function:
[-999999.999
Enter the high reference value
[RPM] for the motor shaft speed
and the high feedback value, see
also parameter 5-58 Term. 33 High
Ref./Feedb. Value. Select terminal 29
Danfoss A/S © 10/2019 All rights reserved.
®
VLT
AutomationDrive FC 301/302
5-53 Term. 29 High Ref./Feedb. Value
Range:
5-54 Pulse Filter Time Constant #29
Range:
100 ms
*
Input
(Hz)
5-55 Term. 33 Low Frequency
Range:
100 Hz
*
5-56 Term. 33 High Frequency
Range:
Size
related
*
5-57 Term. 33 Low Ref./Feedb. Value
Range:
Size
related
*
5-58 Term. 33 High Ref./Feedb. Value
Range:
Size
related
*
Function:
as a digital input
(parameter 5-02 Terminal 29 Mode =
[0] input (default) and
parameter 5-13 Terminal 29 Digital
Input = applicable value).
This parameter is available for FC
302 only.
Function:
[1 - 1000 ms] Enter the pulse filter time constant.
The pulse filter dampens
oscillations of the feedback signal, if
there is much noise in the system
this is an advantage. A high time
constant value results in better
dampening but also increases the
time delay through the filter.
Function:
[0 - 110000
Enter the low frequency
Hz]
corresponding to the low motor
shaft speed (that is low reference
value) in parameter 5-57 Term. 33
Low Ref./Feedb. Value.
Function:
[0 - 110000
Enter the high frequency
Hz]
corresponding to the high motor
shaft speed (that is high reference
value) in parameter 5-58 Term. 33
High Ref./Feedb. Value.
Function:
[-999999.999
Enter the low reference value [RPM]
- 999999.999
for the motor shaft speed. This is
Reference-
also the low feedback value, see
FeedbackUnit]
also parameter 5-52 Term. 29 Low
Ref./Feedb. Value.
Function:
[-999999.999
Enter the high reference value
- 999999.999
[RPM] for the motor shaft speed.
Reference-
See also parameter 5-53 Term. 29
FeedbackUnit]
High Ref./Feedb. Value.
M0013101