Parameter Descriptions
Display lines 2 and 3 in the LCP show the status for timed
actions mode (parameter 0-23 Display Line 2 Large and
parameter 0-24 Display Line 3 Large, setting [1643] Timed
Actions Status).
NOTICE
3
3
A change in mode via the digital inputs can only take
place if parameter 23-08 Timed Actions Mode is set for [0]
Times Actions Auto.
If commands are applied simultaneously to the digital
inputs for constant OFF and constant ON, the timed
actions mode changes to timed actions auto and the 2
commands are disregarded.
If parameter 0-70 Date and Time is not set or the
frequency converter is set to hand-on mode or OFF
mode (for example via the LCP), the timed actions mode
is changed to [0] Disabled.
The timed actions have a higher priority than the same
actions/commands activated by the digital inputs or the
smart logic controller.
The actions programmed in timed actions are merged with
corresponding actions from digital inputs, control word via
bus, and smart logic controller, according to merge rules
set up in parameter group 8-5* Digital/Bus.
NOTICE
Program the clock (parameter group 0-7* Clock Settings)
correctly for timed actions to function.
NOTICE
When mounting VLT
battery back-up of the date and time is included.
NOTICE
The PC-based configuration tool MCT 10 Set-up Software
comprises a special guide for easy programming of
timed actions.
272
®
VLT
AutomationDrive FC 301/302
®
Analog I/O Option MCB 109, a
Danfoss A/S © 10/2019 All rights reserved.
23-00 ON Time
Array [10]
Range:
Function:
Size
[ 0 - 0 ]
Sets the ON time for the timed
related
action.
*
NOTICE
The frequency converter has
no back-up of the clock
function. The set date/time
resets to default (2000-01-01
00:00) after a power-down
unless a real-time clock-
module with back-up is
installed. In
parameter 0-79 Clock Fault, it is
possible to program a warning
if the clock has not been set
properly, for example after a
power-down.
23-01 ON Action
Array [10]
Option:
Function:
NOTICE
For options [32] Set digital out
A low–[43] Set digital out F
high, see also parameter group
5-3* Digital Outputs and
parameter group 5-4* Relays.
Select the action during ON time.
See parameter 13-52 SL Controller
Action for descriptions of the
options.
[0]
DISABLED
*
[1]
No action
[2]
Select set-up 1
[3]
Select set-up 2
[4]
Select set-up 3
[5]
Select set-up 4
[10]
Select preset
ref 0
[11]
Select preset
ref 1
[12]
Select preset
ref 2
[13]
Select preset
ref 3
[14]
Select preset
ref 4
[15]
Select preset
ref 5