Parameter Descriptions
18-45 Analog Out X49/11
Range:
Function:
0
[0 - 30 ]
Shows the actual value at output of
*
terminal X49/11 in V or mA. The
value reflects the selection in
parameter 36-60 Terminal X49/11
Analogue Output.
3.18.3 18-5* Active Alarms/Warnings
The parameters in this group show the numbers of
currently active alarms or warnings.
18-55 Active Alarm Numbers
Range:
Function:
0
[0 - 65535 ]
This parameter contains an array of
*
up to 20 alarms that are currently
active. The value 0 means no alarm.
18-56 Active Warning Numbers
Range:
Function:
0
[0 - 65535 ]
This parameter contains an array of
*
up to 20 warnings that are
currently active. The value 0 means
no warning.
18-60 Digital Input 2
Range:
Function:
0
[0 - 65535 ]
Shows the signal states from the
*
active digital inputs.
18-70 Mains Voltage
Range:
Function:
0 V
[0 - 1000 V]
Shows the mains line-to-line
*
voltage.
18-71 Mains Frequency
Range:
Function:
0 Hz
[-100 - 100
Shows the mains frequency.
*
Hz]
18-72 Mains Imbalance
Range:
Function:
0 %
[0 - 100 %]
Shows the maximum imbalance for
*
the 3 mains line-to-line
measurements.
18-75 Rectifier DC Volt.
Range:
Function:
0 V
[0 - 10000 V] Shows the DC voltage measured on
*
the rectifier module.
M0013101
Programming Guide
0 = No signal.
1 = Connected signal.
Danfoss A/S © 10/2019 All rights reserved.
18-90 Process PID Error
Range:
Function:
0 %
[-200 -
Give the present error value used
*
200 %]
by the process PID controller.
18-91 Process PID Output
Range:
Function:
0 %
[-200 -
Give the present raw output value
*
200 %]
from the process PID controller.
18-92 Process PID Clamped Output
Range:
Function:
0 %
[-200 -
Give the present output value from
*
200 %]
the process PID controller after the
clamp limits have been observed.
18-93 Process PID Gain Scaled Output
Range:
Function:
0 %
[-200 -
Give the present output value from
*
200 %]
the process PID controller after the
clamp limits have been observed,
and the resulting value has been
gain scaled.
3.19 Parameters: 19-** Application
Parameters
Parameters in this group are available when VLT
Control Option MCO 305 is installed in the frequency
converter. For information about the option, see the VLT
Motion Control Option MCO 305 Operating Instructions.

3.20 Parameters: 22-** Appl. Functions

22-00 External Interlock Delay
Range:
Function:
0 s
[0 - 600 s]
*
3.21 Parameters: 23-** Time-based
Functions
3.21.1 23-0* Timed Actions
Use timed actions for actions performed on a daily or
weekly basis, for example different references for working
hours/non-working hours. Up to 10 timed actions can be
programmed in the frequency converter. Select the timed
action number from the list when entering parameter
group 23-** Time-based Functions from the LCP.
Parameter 23-00 ON Time and parameter 23-04 Occurrence
then refer to the selected timed action number. Each
timed action is divided into an ON time and an OFF time,
in which 2 different actions may be performed.
3
3
®
Motion
®