Parameter Descriptions
5-40 Function Relay
Option:
Function:
[72]
Logic rule 2
See parameter group 13-4* Smart
Logic Control. If logic rule 2 in SLC is
true, the output goes high.
Otherwise, it is low.
[73]
Logic rule 3
See parameter group 13-4* Smart
Logic Control. If logic rule 3 in SLC is
true, the output goes high.
Otherwise, it is low.
[74]
Logic rule 4
See parameter group 13-4* Smart
Logic Control. If logic rule 4 in SLC is
true, the output goes high.
Otherwise, it is low.
[75]
Logic rule 5
See parameter group 13-4* Smart
Logic Control. If logic rule 5 in SLC is
true, the output goes high.
Otherwise, it is low.
[79]
PE Power Off
[80]
SL digital
See parameter 13-52 SL Controller
output A
Action. Output A is low on smart
logic action [32] Set digital out A
low. Output A is high on smart
logic action [38].
[81]
SL digital
See parameter 13-52 SL Controller
output B
Action. Output B is low on smart
logic action [33] Set digital out B
low. Output B is high on smart
logic action [39].
[82]
SL digital
See parameter 13-52 SL Controller
output C
Action. Output C is low on smart
logic action [34] Set digital out C
low. Output C is high on smart
logic action [40].
[83]
SL digital
See parameter 13-52 SL Controller 1
output D
Action. Output D is low on smart
logic action [35] Set digital out D
low. Output D is high on smart
logic action [41].
[84]
SL digital
See parameter 13-52 SL Controller
output E
Action. Output E is low on smart
logic action [36] Set digital out E
low. Output E is high on smart logic
action [42].
[85]
SL digital
See parameter 13-52 SL Controller
output F
Action. Output F is low on smart
logic action [37] Set digital out F
low. Output F is high on smart logic
action [43].
NOTICE
[96]
Reverse After
Ramp
This option is available only
with software version 48.XX.
M0013101
Programming Guide
5-40 Function Relay
Option:
[98]
[120]
[121]
[122]
[123]
Danfoss A/S © 10/2019 All rights reserved.
Function:
See the description in parameter
group 5-3* Digital Outputs.
NOTICE
Virtual Master
Dir.
This option is available only
with software version 48.XX.
See the description in parameter
group 5-3* Digital Outputs.
Local ref
Output is high when
active
parameter 3-13 Reference Site = [2]
Local or when
parameter 3-13 Reference Site = [0]
Linked to hand auto at the same
time as the LCP is in hand-on
mode.
Reference site
set in
parameter 3-1
3 Reference
Site
Reference site:
Local
parameter 3-13
Reference Site
[2] Local
Reference site:
Remote
parameter 3-13
Reference Site
[1] Remote
Reference site:
Linked to
Hand/ Auto
Hand
Hand⇒off
Auto⇒off
Auto
Table 3.23 Local Reference Active
Remote ref
Output is high when
active
parameter 3-13 Reference Site = [1]
Remote or [0] Linked to hand/auto
while the LCP is in auto-on mode.
See Table 3.23.
No alarm
Output is high when no alarm is
present.
Start
Output is high when the start
command
command is high (that is via digital
activ
input, bus connection, [Hand On],
or [Auto On]), and a stop has been
last command.
3
3
Local
Remote
referen
referenc
ce
e
active
active
[120]
[121]
1
0
0
1
1
0
1
0
0
0
0
1
153