Parameter Descriptions
42-24 Restart Behaviour
Option:
[0]
Manual
*
3
3
[1]
Automatic
42-30 External Failure Reaction
Option:
[0]
STO
*
[1]
SS1-a
[2]
SS1-b
42-31 Reset Source
Option:
[0]
Drive Reset
*
[1]
Drive Safe
Reset
[2]
Safe Option
DI2_A
42-33 Parameter Set Name
Range:
Size
related
*
42-35 S-CRC Value
Range:
Size
related
*
42-36 Level 1 Password
Range:
Size
related
*
42-37 Level 1 Password Buffer
Range:
Size
related
*
308
Function:
In case of an activated safety
function, the safety option waits for
a RESET signal from the user.
In case of an activated safety
function, the safety option restarts
automatically.
Function:
Select the option when Safe Torque
Off (STO) has to be executed when
there is an external failure.
Select the option when Safe Stop
(SS1-a) has to be executed when
there is an external failure.
Select the option when Safe Stop
(SS1-b) has to be executed when
there is an external failure.
Function:
By selecting Drive Safe Reset, only
the safety option is reset. If
parameter 42-31 Reset Source is set
to [1] Drive Safe Reset, configure [3]
Safe Option Reset in parameter 8-14
Configurable Control Word CTW.
Function:
[0 - 8 ]
Name of the safe parameter Set.
Recommended to enter text with
characters to avoid a bad customi-
zation data error.
Function:
[0 - 65535 ]
Function:
[0 - 8 ]
Function:
[0 - 8 ]
Danfoss A/S © 10/2019 All rights reserved.
®
VLT
AutomationDrive FC 301/302
42-40 Type
Parameter to select the type of SS1 safety function.
Option:
[0]
*
[1]
[2]
42-41 Ramp Profile
Option:
[0]
*
[2]
42-42 Delay Time
Range:
1 s
*
42-43 Delta T
Range:
2 %
*
42-44 Deceleration Rate
Range:
1500 /s
*
42-45 Delta V
Range:
120 RPM
42-46 Zero Speed
Range:
10 RPM
*
42-47 Ramp Time
Range:
1 s
*
Function:
Delay
Ramp (slope)
Select this option to request a SS1
to decelerate at least with the
steepness of the deceleration ramp,
even under heavy load. The safety
option initiates a stop signal to
drive and monitors the controlled
braking by monitoring the braking
ramp.
Ramp (time)
Select this option to enable a SS1
safety option with a deceleration
time and tolerable speed.
Function:
Linear
The ramp follows a linear curve.
S-ramp Const
The ramp follows a S-ramp.
Time
Function:
[0.1 - 3600 s] Configure the time during which
STO must be activated.
Function:
[0 - 99 %]
Δ T subtracts from the time in
parameter 42-42 Delay Time to get
motor to stop before the timer
expires.
Function:
[1 - 30000 /s] Deceleration rate for the SS1 slope-
based ramp type.
Function:
[1 - 10000
Tolerance between calculated and
*
RPM]
actual speed that the safety option
allows.
Function:
[1 - 600
When this speed is reached, the
RPM]
safety option activates the STO.
Function:
[0.1 - 3600 s] Time to ramp down to 0 RPM.
M0013101