Parameter Descriptions
13-10 Comparator Operand
Option:
Function:
Mode or parameter 4-17 Torque Limit
Generator Mode.
[66]
Current Limit
The motor current exceeds the
value in parameter 4-18 Current
Limit.
[67]
Out of current
The motor current is outside the
range
range set in parameter 4-18 Current
Limit.
[68]
Below I low
The motor current is lower than the
value in parameter 4-50 Warning
Current Low.
[69]
Above I high
The motor current is higher than
the value in parameter 4-51 Warning
Current High.
[70]
Out of speed
The speed is outside the range set
range
in parameter 4-52 Warning Speed
Low and parameter 4-53 Warning
Speed High.
[71]
Below speed
The output speed is lower than the
value in parameter 4-52 Warning
low
Speed Low.
[72]
Above speed
The output speed is higher than
high
the value in parameter 4-53 Warning
Speed High.
[75]
Out of
The feedback is outside the range
feedback
set in parameter 4-56 Warning
range
Feedback Low and
parameter 4-57 Warning Feedback
High.
[76]
Below
The feedback is lower than the limit
feedback low
set in parameter 4-56 Warning
Feedback Low.
[77]
Above
The feedback exceeds the limit set
feedback high
in parameter 4-57 Warning Feedback
High.
[80]
Thermal
This operand becomes true when
warning
the frequency converter detects any
thermal warning, for instance when
the temperature exceeds the limit
in the motor, the frequency
converter, the brake resistor, or
thermistor.
[82]
Mains out of
The mains voltage is outside the
range
specified voltage range.
[85]
Warning
If a warning is triggered, this
operand gets the warning number.
[86]
Alarm (trip)
A trip alarm is active.
[87]
Alarm (trip
A trip lock alarm is active.
lock)
M0013101
Programming Guide
13-10 Comparator Operand
Option:
[90]
[91]
[92]
[93]
[94]
[100]
[101]
[102]
[103]
[104]
[105]
[110]
[111]
[112]
[113]
[114]
[115]
[120]
[121]
[122]
[123]
[124]
[125]
[126]
[127]
[130]
[131]
[132]
[133]
[134]
[135]
[150]
Danfoss A/S © 10/2019 All rights reserved.
Function:
Bus OK
Active communication (no timeout)
via the serial communication port.
Torque limit &
If the frequency converter has
stop
received a stop signal and is at the
torque limit, the signal is logic 0.
Brake fault
The brake IGBT is short-circuited.
(IGBT)
Mech. brake
The mechanical brake is active.
control
Safe stop
active
Comparator 0
The result of comparator 0.
Comparator 1
The result of comparator 1.
Comparator 2
The result of comparator 2.
Comparator 3
The result of comparator 3.
Comparator 4
The result of comparator 4.
Comparator 5
The result of comparator 5.
Logic rule 0
The result of logic rule 0.
Logic rule 1
The result of logic rule 1.
Logic rule 2
The result of logic rule 2.
Logic rule 3
The result of logic rule 3.
Logic rule 4
The result of logic rule 4.
Logic rule 5
The result of logic rule 5.
SL Time-out 0
The result of SLC timer 0.
SL Time-out 1
The result of SLC timer 1.
SL Time-out 2
The result of SLC timer 2.
SL Time-out 3
The result of SLC timer 3.
SL Time-out 4
The result of SLC timer 4.
SL Time-out 5
The result of SLC timer 5.
SL Time-out 6
The result of SLC timer 6.
SL Time-out 7
The result of SLC timer 7.
Digital input
Digital input 18 (high=true).
DI18
Digital input
Digital input 19 (high=true).
DI19
Digital input
Digital input 27 (high=true).
DI27
Digital input
Digital input 29 (high=true).
DI29
Digital input
Digital input 32 (high=true).
DI32
Digital input
Digital input 33 (high=true).
DI33
SL digital
Use the result of the SLC output A.
output A
3
3
207

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 302

Table of Contents