Parameter Descriptions
30-50 Heat Sink Fan Mode
Option:
3
3
[1]
Reduced
Acoustics
[2]
Standard
[3]
Cooler
Operation
3.22.6 30-8* Compatibility (I)
30-80 d-axis Inductance (Ld)
Range:
Size
related
1000.000 mH]
*
30-81 Brake Resistor (ohm)
Range:
Size
related
65535.00
*
Ohm]
30-83 Speed PID Proportional Gain
Range:
Size
related
*
30-84 Process PID Proportional Gain
Range:
Size
related
*
282
Function:
Use parameter 14-52 Fan Control to
control the minimum fan speed.
The simple profile is a passive fan
control based on the current
temperature state of the frequency
converter. This option represents
the classic operating behavior of
fans.
Function:
[0.000 -
Enter the value of the d-axis
inductance. Obtain the value from
the permanent magnet motor
datasheet. The d-axis inductance
cannot be found by performing an
AMA.
Function:
Set the brake resistor value in Ω.
[ 0.01 -
This value is used for monitoring
the power to the brake resistor in
parameter 2-13 Brake Power
Monitoring. This parameter is only
active in frequency converters with
an integral dynamic brake.
Function:
[0 - 1 ]
Enter the speed controller propor-
tional gain. Quick control is
obtained at high amplification.
However, if amplification is too
great, the process may become
unstable.
Function:
[0 - 10 ]
Enter the process controller propor-
tional gain. Quick control is
obtained at high amplification.
However, if amplification is too
great, the process may become
unstable.
Danfoss A/S © 10/2019 All rights reserved.
®
VLT
AutomationDrive FC 301/302
30-85 Motor Frequency
Range:
50
[20 - 1000 Hz]
*
Parameters for configuring the wireless LCP 103.
30-90 SSID
Range:
Size
related
*
30-91 Channel
Range:
5
*
30-92 Password
Range:
Size
related
*
30-97 Wifi Timeout Action
Select which action to execute if a local reference (hand-on
mode) or a remote reference (auto-on mode) is set via the
wireless connection and the connection is lost.
Option:
[0]
*
[1]
30-98 Remote SSID
Range:
Size
related
*
Function:
NOTICE
Changing this parameter affects the
settings of other parameters.
Select the motor frequency value from the
motor nameplate data.
Function:
[1 - 32 ]
Enter the wireless network name
(SSID). The default value is:
Danfoss_<Serial number of the
frequency converter>. The serial
number is in
parameter 15-51 Frequency Converter
Serial Number.
Function:
[1 - 11 ]
Enter the wireless channel number.
The default channel number is 5.
Change the channel number, if
there is an interference from other
wireless networks. Recommended
channels:
USA territory: 1, 6, 11.
Europe: 1, 7, 13.
Function:
[8 - 48 ]
Enter the wireless network
password. Password length: 8–48
characters.
Function:
Do Nothing
The frequency converter does not
do any extra actions.
Stop Motor
The frequency converter stops the
motor (if the motor was started via
a wireless connection).
Function:
[1 - 32 ]
M0013101