Parameter Descriptions
14-20 Reset Mode
Option:
[9]
Automatic
reset x 9
[10]
Automatic
3
3
reset x 10
[11]
Automatic
reset x 15
[12]
Automatic
reset x 20
[13]
Infinite auto
reset
[14]
Reset at
power-up
14-21 Automatic Restart Time
Range:
Size
related
*
14-22 Operation Mode
Option:
234
Function:
Select this option for continuous
resetting after tripping.
Function:
[0 - 3600 s]
Enter the time interval from trip to
start of the automatic reset
function. This parameter is active
when parameter 14-20 Reset Mode is
set to [1]–[13] Automatic reset.
Function:
Use this parameter to specify
normal operation, to perform tests,
or to initialize all parameters except
parameter 15-03 Power Up's,
parameter 15-04 Over Temp's, and
parameter 15-05 Over Volt's. This
function is active only when the
power is cycled to the frequency
converter.
Select [0] Normal operation for
normal operation of the frequency
converter with the motor in the
selected application.
Select [1] Control card test to test
the analog and digital inputs and
outputs and the +10 V control
voltage. The test requires a test
connector with internal
connections. Use the following
procedure for the control card test:
1.
Select [1] Control card test.
2.
Disconnect the mains
supply and wait for the
indicator light in the
display to go out.
3.
Set switches S201 (A53)
and S202 (A54) to ON/I.
4.
Insert the test plug (see
Illustration 3.63).
Danfoss A/S © 10/2019 All rights reserved.
®
VLT
AutomationDrive FC 301/302
14-22 Operation Mode
Option:
Function:
5.
Connect to mains supply.
6.
Carry out various tests.
7.
The results are shown on
the LCP and the frequency
converter moves into an
infinite loop.
8.
Parameter 14-22 Operation
Mode is automatically set
to normal operation. Carry
out a power cycle to start
up in normal operation
after a control card test.
If the test is OK
LCP readout: Control card OK.
Disconnect the mains supply and
remove the test plug. The green
indicator light on the control card
lights up.
If the test fails
LCP readout: Control card I/O
failure.
Replace the frequency converter or
control card. The red indicator light
on the control card is turned on.
Test plugs (connect the following
terminals to each other): 18 - 27 -
32; 19 - 29 - 33; 42 - 53 - 54
12
13
18
19
27
29
32
33 20
37
FC 302
12 13
18
19
27
32
33
20
FC 301
39 42
50
53
54
55
FC 301 &
FC 302
Illustration 3.63 Test Plugs
Select [2] Initialisation to reset all
parameter values to default
settings, except for:
Parameter 15-03 Power Up's,
parameter 15-04 Over Temp's, and
parameter 15-05 Over Volt's. The
frequency converter resets during
the next power-up.
M0013101