Parameter Descriptions
3-75 Ramp 4 S-ramp Ratio at Accel. Start
Range:
50 %
*
3
3
3-76 Ramp 4 S-ramp Ratio at Accel. End
Range:
50 %
*
3-77 Ramp 4 S-ramp Ratio at Decel. Start
Range:
50 %
*
3-78 Ramp 4 S-ramp Ratio at Decel. End
Range:
50 %
*
3.4.8 3-8* Other Ramps
3-80 Jog/Homing Ramp Time
Range:
Size
related
s]
*
100
Function:
[ 1 - 99 %]
Enter the proportion of the total
ramp-up time (parameter 3-71 Ramp
4 Ramp up Time) in which the
acceleration torque increases. The
larger the percentage value, the
greater the jerk compensation
achieved, and thus the lower the
torque jerks in the application.
Function:
[ 1 - 99 %]
Enter the proportion of the total
ramp-up time (parameter 3-71 Ramp
4 Ramp up Time) in which the
acceleration torque decreases. The
larger the percentage value, the
greater the jerk compensation
achieved, and thus the lower the
torque jerks in the application.
Function:
[ 1 - 99 %]
Enter the proportion of the total
ramp-down time
(parameter 3-72 Ramp 4 Ramp Down
Time) where the deceleration
torque increases. The larger the
percentage value, the greater the
jerk compensation achieved, and
thus the lower the torque jerks in
the application.
Function:
[ 1 - 99 %]
Enter the proportion of the total
ramp-down time
(parameter 3-72 Ramp 4 Ramp Down
Time) where the deceleration
torque decreases. The larger the
percentage value, the greater the
jerk compensation achieved, and
thus the lower the torque jerks in
the application.
Function:
[0.01 - 3600
Enter the jog ramp time, that is the
acceleration/deceleration time
between 0 RPM and the rated
motor frequency n
Danfoss A/S © 10/2019 All rights reserved.
®
VLT
AutomationDrive FC 301/302
3-80 Jog/Homing Ramp Time
Range:
P 4-13 RPM
high limit
Motor speed
Jog speed
P 4-11 RPM
Illustration 3.27 Jog Ramp Time
Par .  3 − 80  =  
3-81 Quick Stop Ramp Time
Range:
Size
related
*
. Ensure that the
s
Function:
resulting output current required
for the given jog ramp time does
not exceed the current limit in
parameter 4-18 Current Limit. The
jog ramp time starts after activation
of a jog signal via the LCP, a
selected digital input, or the serial
communication port. When jog
state is disabled, then the normal
ramping times are valid.
RPM
P 1-25
P 3-19
low limit
t jog
P 3-80
P 3-80
Ramp up
Ramp down
(acc)
(dec)
t
  s  x n
  RPM
jog
s
 Δ  jog speed  par .  3  −  19   RPM
Function:
[0.01 - 3600
Enter the quick–stop ramp-down
s]
time, that is the deceleration time
from the synchronous motor speed
to 0 RPM. Ensure that no resulting
overvoltage occurs in the inverter
due to regenerative operation of
the motor required to achieve the
given ramp-down time. Ensure also
that the generated current required
to achieve the given ramp-down
time does not exceed the current
limit (set in parameter 4-18 Current
Limit). Quick stop is activated with
a signal on a selected digital input,
or via the serial communication
port.
t jog
Time
M0013101