Parameter Descriptions
4-24 Brake Check Limit Factor
Range:
Function:
4-25 Power Limit Motor Factor Source
Select the input that scales the value in parameter 4-82 Power
Limit Motor Mode from 0% to 100%.
Option:
Function:
[0]
No function
*
[2]
Analog in 53
[4]
Analog in 53
inv
[6]
Analog in 54
[8]
Analog in 54
inv
[10]
Analog in
X30-11
[12]
Analog in
X30-11 inv
[14]
Analog in
X30-12
[16]
Analog in
X30-12 inv
4-26 Power Limit Gener. Factor Source
Select the input that scales the value in parameter 4-83 Power
Limit Generator Mode from 0% to 100%.
Option:
Function:
[0]
No function
*
[2]
Analog in 53
[4]
Analog in 53
inv
[6]
Analog in 54
[8]
Analog in 54
inv
[10]
Analog in
X30-11
[12]
Analog in
X30-11 inv
[14]
Analog in
X30-12
[16]
Analog in
X30-12 inv
M0013101
Programming Guide
connected to analog input
53.
Parameter 4-24 Brake Check
Limit Factor is set to 80%.
Danfoss A/S © 10/2019 All rights reserved.
3.5.2 4-3* Motor Feedback Monitoring
The parameter group includes monitoring and handling of
motor feedback devices, such as encoders, resolvers, and
so on.
4-30 Motor Feedback Loss Function
Option:
Function:
This function is used to monitor
consistency in the feedback signal,
that is if the feedback signal is
available.
Select which action the frequency
converter should take if a feedback
fault is detected. The selected
action is to take place when the
feedback signal differs from the
output speed by the value set in
parameter 4-31 Motor Feedback
Speed Error for longer than the
value set in parameter 4-32 Motor
Feedback Loss Timeout.
[0]
Disabled
[1]
Warning
[2]
Trip
[3]
Jog
[4]
Freeze Output
[5]
Max Speed
[6]
Switch to
Open Loop
[7]
Select Setup 1
[8]
Select Setup 2
[9]
Select Setup 3
[10]
Select Setup 4
[11]
Stop & Trip
Warning 90, Feedback monitor is active as soon as the value
in parameter 4-31 Motor Feedback Speed Error is exceeded,
regardless of the setting in parameter 4-32 Motor Feedback
Loss Timeout. Warning/Alarm 61, Feedback Error is related to
the motor feedback loss function.
4-31 Motor Feedback Speed Error
Range:
Function:
300 RPM
[1 - 600
Select the maximum allowed error
*
RPM]
in speed (output speed vs.
feedback).