Parameter Descriptions
6-13 Terminal 53 High Current
Range:
3
3
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Size
related
- 999999.999
*
Reference-
FeedbackUnit]
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Size
related
- 999999.999
*
Reference-
FeedbackUnit]
6-16 Terminal 53 Filter Time Constant
Range:
0.001 s
*
3.7.3 6-2* Analog Input 2
Parameters for configuring the scaling and limits for analog
input 2 (terminal 54).
6-20 Terminal 54 Low Voltage
Range:
Size
related
6-21 V]
*
164
Function:
reference/feedback set in
parameter 6-15 Terminal 53 High
Ref./Feedb. Value.
Function:
[-999999.999
Enter the analog input scaling value
that corresponds to the low
voltage/low current set in
parameter 6-10 Terminal 53 Low
Voltage and parameter 6-12 Terminal
53 Low Current.
Function:
[-999999.999
Enter the analog input scaling value
that corresponds to the maximum
reference feedback value set in
parameter 6-11 Terminal 53 High
Voltage and parameter 6-13 Terminal
53 High Current.
Function:
NOTICE
[0.001 - 10 s]
This parameter cannot be
adjusted while the motor is
running.
Enter the filter time constant. This
constant is a first-order digital low-
pass filter time for suppressing
electrical noise in terminal 53. A
high value improves dampening
but also increases the delay
through the filter.
Function:
[ -10.00 - par.
Enter the low voltage value. This
analog input scaling value should
correspond to the minimum
reference value set in
parameter 3-02 Minimum Reference.
See also chapter 3.4 Parameters: 3-**
Reference/Ramps.
Danfoss A/S © 10/2019 All rights reserved.
®
VLT
AutomationDrive FC 301/302
6-21 Terminal 54 High Voltage
Range:
10 V
*
6-22 Terminal 54 Low Current
Range:
Size
related
*
6-23 Terminal 54 High Current
Range:
20 mA
*
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
Size
related
*
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Size
related
*
6-26 Terminal 54 Filter Time Constant
Range:
0.001 s
*
Function:
[ par. 6-20 -
Enter the high voltage value. This
10 V]
analog input scaling value should
correspond to the high reference
feedback value set in
parameter 6-25 Terminal 54 High
Ref./Feedb. Value.
Function:
[ 0 - par. 6-23
Enter the low current value. This
mA]
reference signal should correspond
to the minimum reference value,
set in parameter 3-02 Minimum
Reference. Enter the value that
exceeds 2 mA to activate the live
zero timeout function in
parameter 6-01 Live Zero Timeout
Function.
Function:
[ par. 6-22 -
Enter the high current value
20 mA]
corresponding to the high reference
feedback value set in
parameter 6-25 Terminal 54 High
Ref./Feedb. Value.
Function:
[-999999.999
Enter the analog input scaling value
- 999999.999
that corresponds to the minimum
Reference-
reference feedback value set in
FeedbackUnit]
parameter 3-02 Minimum Reference.
Function:
[-999999.999
Enter the analog input scaling value
- 999999.999
that corresponds to the maximum
Reference-
reference feedback value set in
FeedbackUnit]
parameter 3-03 Maximum Reference.
Function:
NOTICE
[0.001 - 10 s]
This parameter cannot be
adjusted while the motor is
running.
Enter the filter time constant. This is
a first-order digital low-pass filter
time constant for suppressing
electrical noise in terminal 54.