7.2 Parameter list
p0318[0...n]

Motor stall current / Mot I_standstill

Access level: 4
Can be changed: C2(3)
Unit group: -
Min:
0.00 [Arms]
Description:
Sets the stall current for synchronous motors (p0300 = 2xx), as well as for synchronous reluctance motors (p0300 =
6xx).
NOTICE
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note
The parameter is used for the I2t monitoring of the motor (refer to p0611).
This parameter is not used for induction motors (p0300 = 1xx).
p0320[0...n]
Motor rated magnetizing current/short-circuit current / Mot I_mag_rated
Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.000 [Arms]
Description:
Induction motors:
Sets the rated motor magnetizing current.
For p0320 = 0.000 the magnetizing current is internally calculated and displayed in r0331.
Synchronous motors:
Sets the rated motor short-circuit current.
NOTICE
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note
The magnetizing current p0320 for induction motors is reset when quick commissioning is exited with p3900 > 0.
If, for induction motors, the magnetizing current p0320 is changed outside the commissioning phase (p0010 > 0), then
the magnetizing inductance p0360 is changed so that the EMF r0337 remains constant.
p0322[0...n]

Maximum motor speed / Mot n_max

Access level: 1
Can be changed: C2(1, 3)
Unit group: -
Min:
0.0 [rpm]
Description:
Sets the maximum motor speed.
Dependency:
See also: p1082
NOTICE
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0322 is changed during quick commissioning (p0010 = 1), the maximum speed p1082, which is also associated
with quick commissioning, is pre-assigned accordingly.
Note
The parameter has no significance for a value of p0322 = 0.
520
Calculated: -
Scaling: -
Unit selection: -
Max:
10000.00 [Arms]
Calculated: -
Scaling: -
Unit selection: -
Max:
5000.000 [Arms]
Calculated: -
Scaling: -
Unit selection: -
Max:
210000.0 [rpm]
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: FloatingPoint32
Dynamic index: MDS, p0130
Function diagram: 8017
Factory setting:
0.00 [Arms]
Data type: FloatingPoint32
Dynamic index: MDS, p0130
Function diagram: -
Factory setting:
0.000 [Arms]
Data type: FloatingPoint32
Dynamic index: MDS, p0130
Function diagram: -
Factory setting:
0.0 [rpm]