Figure 6-65
Procedure for switching off an uncontrolled motor:
1. The speed-controlled motor turns with minimum speed p1080.
2. The control deviation of the technology controller is less than -p2373.
3. Time p2375 has expired.
The converter accelerates the speed-controlled motor with ramp-up time p1120 to the
activation/deactivation speed p2378. Until the activation/deactivation speed p2378 is
attained, the converter deactivates the technology controller temporarily.
4. After shutdown delay p2386, the converter disconnects an uncontrolled motor.
Sequence for activating and deactivating the M
Table 6-94
p2371 specifies the sequence for activating and deactivating the motors
p2371
→ → → Sequence for activating motors → → →
→ → → Sequence for deactivating motors → → →
Stage 1
1
M
1
2
M
1
3
M
1
Parameter
Number
p2200
p2251
p2370
p2371
p2372
p2373
p2374
p2375
p2376
p2377
p2378
r2379
p2380
p2381
p2382
p2383
p2384
p2385
p2386
p2387
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Deactivate uncontrolled motors M
Stage 2
Stage 3
M
+M
1
2
M
M
2
1
Name
Technology controller enable
Technology controller mode
Cascade control enable
Cascade control configuration
Cascade control motor selection mode
Cascade control activation threshold
Cascade control activation delay
Cascade control deactivation delay
Cascade control overload threshold
Cascade control interlock time
Cascade control activation/deactivation speed
Cascade control status word
Cascade control operating hours
Cascade control maximum time for continuous mode
Cascade control absolute operating time limit
Cascade control deactivation sequence
Cascade control motor switch-on delay
Cascade control stop time activation speed
Cascade control motor switch-off delay
Cascade control stop time deactivation speed
... M
1
2
... M
motors
1
2
Power of the activated M
with the speed-controlled DM motor
1 × M
M
1
M
, M
1
+M
M
2
1
Advanced commissioning
6.6 Technology controller
... M
motors compared
1
3
2 × M
D
---
---
2
M
2
Factory setting
0
0
0
0
0
20%
30 s
30 s
25%
0 s
50%
---
0 h
24 h
24 h
0
0 s
0 s
0 s
0 s
D