Dynamic Monitoring Of Sto Feedback For Fsa … Fsg; Connection 3Sk2 Inside A Control Cabinet For Fsh And Fsj - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

T
≥ 30 ms
1
T
≥ 20 ms
2
Figure 4-30
Figure 4-31
Static monitoring of STO feedback at start-up is sufficient for the converters FSH and FSJ.
Modular 3RK3 safety system
You can use the following outputs to control the failsafe digital inputs in the converter:
● The failsafe digital outputs in the central units of the 3RK3 modular safety system
● The failsafe digital outputs in the EM 2/4F-DI 2F-DO expansion module
● The failsafe digital outputs in the EM 4F-DO expansion module.
● The failsafe relay outputs in the EM 4/8F-RO expansion module
● 2 individual relay contacts of the EM 2/4F-DI 1/2F-RO expansion module
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
In case of deviating feedback, the safety relay must select the STO function
and indicate an error.
Dynamic monitoring of STO feedback for FSA ... FSG

Connection 3SK2 inside a control cabinet for FSH and FSJ

Wiring
4.2 Control interfaces
135