Line Harmonics Filter - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Article number
Converter frame size Rated power (kW)
400 V converters
FSH
FSJ
690 V converters
FSH
FSJ
2.6.3

Line harmonics filter

Note
Line harmonics filters are available as optional components for 400 V converters of frame sizes
FSB to FSG.
The line harmonics filters reshape the distorted current back to the desired sinusoidal
waveform. With the line harmonics filters, the converter fulfills the IEEE 519 standards.
If you use a line harmonics filter, you do not need a line reactor or a line filter.
When using the line harmonics filter, observe the following restrictions:
● The permissible line voltage is 380 V ... 415 V 3 AC ±10 %.
● The operating frequency is 50 Hz.
For technical details refer to the following link:
fn-3440-ecosine-50hz-passive-harmonic-filters/)
Article number
400 V Converter
frame size
FSB
FSC
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
315
355 ... 400
450
500 ... 560
315 ... 400
450
500
560 ... 630
Line harmonics filter
(https://www.schaffner.com/products/download/product/datasheet/
Rated power (kW)
5.5
7.5
11
15
2.6 Optional components
Line reactor
6SL3000-0CE36-3AA0
6SL3000-0CE37-7AA0
6SL3000-0CE38-7AA0
6SL3000-0CE41-0AA0
6SL3000-0CH34-8AA0
6SL3000-0CH36-0AA0
6SL3000-0CH38-4AA0
Line harmonics filter
UAC:FN34406112E2XXJRX
UAC:FN34408112E2XXJRX
UAC:FN344011113E2FAJRX
UAC:FN344015113E2FAJRX
Description
35