Kinetic buffering (Vdc min control)

Overview
Kinetic buffering increases the drive availability. The kinetic buffering utilizes the kinetic energy
of the load to buffer line dips and failures. During a line dip, the converter keeps the motor in the
switched-on state for as long as possible. One second is a typical maximum buffer time.
Precondition
The following conditions have to be fulfilled to use the "kinetic buffering" function
advantageously:
● The driven machine has a sufficiently high inertia.
● The application allows a motor to be braked during a power failure.
Function description
When the line supply dips, the DC-link voltage in the converter decreases. The kinetic buffering
(V
DC min
into slightly regenerative operation. As a consequence, the converter covers its power loss and
the losses in the motor with the kinetic energy of the load. The load speed decreases, but the
DC-link voltage remains constant during the kinetic buffering. After the line supply returns, the
converter immediately resumes normal operation.
Figure 6-90
Parameters
Number
r0056[0...15]
p0210
p1240[D]
428
control) intervenes at an adjustable threshold. The V

Principle mode of operation of kinetic buffering

Name
CO/BO: Status word, closed-loop control
Device supply voltage
Vdc controller configuration (vector control)
control forces the load to go
DC min
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Factory setting
-
400 V
1
SINAMICS G120X converter

Advertisement

Table of Contents
loading

Table of Contents