Co: Free Tec_Ctrl 1 Output Signal / Ftec1 Out_Sig; Ci: Free Tec_Ctrl 1 Limit Maximum Signal Source / Ftec1 Lim Max S_S; Ci: Free Tec_Ctrl 1 Limit Minimum Signal Source / Ftec1 Lim Min S_S; Ci: Free Tec_Ctrl 1 Limit Offset Signal Source / Ftec1 Lim Offs - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

r11194

CO: Free tec_ctrl 1 output signal / Ftec1 out_sig

Access level: 2
Can be changed: -
Unit group: -
Min:
- [%]
Description:
Display and connector output for the output signal of the free technology controller 1.
p11197

CI: Free tec_ctrl 1 limit maximum signal source / Ftec1 lim max s_s

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the signal source for the maximum limit of the free technology controller 1.
Dependency:
See also: p11191
p11198

CI: Free tec_ctrl 1 limit minimum signal source / Ftec1 lim min s_s

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the signal source for the minimum limit of the free technology controller 1.
Dependency:
See also: p11192
p11199

CI: Free tec_ctrl 1 limit offset signal source / Ftec1 lim offs

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the signal source for the limit offset of the free technology controller 1.
p11200
BI: Free tec_ctrl 2 enable / Ftec2 enab
Access level: 2
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the signal source to switch in/switch out the free technology controller 2.
1 signal: The technology controller is switched in.
0 signal: The technology controller is switched out.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
- [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Parameters
7.2 Parameter list
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7030
Factory setting:
- [%]
Data type: Unsigned32 /
FloatingPoint32
Dynamic index: -
Function diagram: 7030
Factory setting:
11191[0]
Data type: Unsigned32 /
FloatingPoint32
Dynamic index: -
Function diagram: 7030
Factory setting:
11192[0]
Data type: Unsigned32 /
FloatingPoint32
Dynamic index: -
Function diagram: 7030
Factory setting:
0
Data type: Unsigned32 / Binary
Dynamic index: -
Function diagram: 7030
Factory setting:
0
907