Change Fault Response Fault Number / Chng Resp F_No; Change Fault Response Response / Chng Resp Resp - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Parameters
7.2 Parameter list
Note
From the signal source set via the connector input, the corresponding lower 16 bits are converted.
p2099[0...1] together with r2094.0...15 and r2095.0...15 forms two connector-binector converters:
Connector input p2099[0] to binector output in r2094.0...15
Connector input p2099[1] to binector output in r2095.0...15
p2100[0...19]

Change fault response fault number / Chng resp F_no

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0
Description:
Selects the faults for which the fault response should be changed
Dependency:
The fault is selected and the required response is set under the same index.
See also: p2101
Note
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
p2101[0...19]

Change fault response response / Chng resp resp

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0
Description:
Sets the fault response for the selected fault.
Value:
0:
1:
2:
3:
5:
6:
Dependency:
The fault is selected and the required response is set under the same index.
See also: p2100
NOTICE
For the following cases, it is not possible to re-parameterize the fault response to a fault:
- fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- fault response is not permissible for the set fault number.
764
NONE
OFF1
OFF2
OFF3
STOP2
Internal armature short-circuit / DC braking
Calculated: -
Scaling: -
Unit selection: -
Max:
65535
Calculated: -
Scaling: -
Unit selection: -
Max:
6
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: Unsigned16
Dynamic index: -
Function diagram: 8050, 8075
Factory setting:
0
Data type: Integer16
Dynamic index: -
Function diagram: 8050, 8075
Factory setting:
0