Rtc Dtc3 Off Time / Rtc Dtc3 T_Off; Bo: Rtc Dtc3 Output / Rtc Dtc3 Output - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Parameters
7.2 Parameter list
Note
DTC: Digital Time Clock (timer)
RTC: Real-time clock
p8432[0...1]

RTC DTC3 off time / RTC DTC3 t_OFF

Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Sets the switch off time in hours and minutes for timer 3 (DTC3).
BO: r8433 = 0 signal:
The condition for the set weekday (p8430) and switch-off time has been fulfilled.
Index:
[0] = Hour (0 ... 23)
[1] = Minute (0 ... 59)
Dependency:
See also: p8409, p8430, r8433
NOTICE
This parameter can only be changed when p8409 = 0.
Note
DTC: Digital Time Clock (timer)
RTC: Real-time clock
r8433.0...1

BO: RTC DTC3 output / RTC DTC3 output

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Display and binector output for the output of timer 3 (DTC3).
Where a weekday is deactivated, the following applies (p8430):
- the binector output for this timer is inactive (r8433.0 = 0).
Where a weekday is activated, the following applies (p8430):
- the ON/OFF time setting (p8431, p8432) for this timer has an instant effect on the binector output (r8433).
Bit field:
Bit
00
01
Dependency:
See also: p8409, p8430, p8431, p8432
NOTICE
This parameter can only be changed when p8409 = 0.
Note
DTC: Digital Time Clock (timer)
RTC: Real-time clock
874
Signal name
Timer on
Timer ON negated
Calculated: -
Scaling: -
Unit selection: -
Max:
59
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
No
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
0
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
-
0 signal
FP
No
-
Yes
-
SINAMICS G120X converter

Advertisement

Table of Contents
loading

Table of Contents