Mastering Critical Applications; Electrically Braking The Motor; Encoderless Speed Control - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Advanced commissioning
6.7 Motor control
8. Set p0340 = 4. The converter again calculates the speed controller parameters.
9. Switch on the motor.
10.Over the complete speed range check as to whether the speed control operates
satisfactorily with the optimized settings.
You have optimized the speed controller.
When necessary, set the ramp-up and ramp-down times of the ramp-function generator
(p1120 and p1121) back to the value before optimization.

Mastering critical applications

The drive control can become unstable for drives with a high load moment of inertia and
gearbox backlash or a coupling between the motor and load that can possibly oscillate. In this
case, we recommend the following settings:
● Increase p1452 (smoothing the speed actual value).
● Increase p1472 (integral time T
● If, after these measures, the speed controller does not operate with an adequate dynamic
performance, then increase p1470 (gain K
Parameters
Table 6-98
Number
p0342[M]
p1452
p1470[D]
p1472[D]
p1496[D]
6.7.4

Electrically braking the motor

Overview
Braking with the motor in generator operation
If the motor brakes the connected load electrically, it converts the kinetic energy of the motor
into electrical energy. The electrical energy E released on braking the load is proportional to the
moment of inertia J of the motor and load and to the square of the speed n. The motor attempts
to pass the energy on to the converter.
398
): T
I

Encoderless speed control

Name
Ratio between the total and motor moments of inertia
Speed controller actual speed value smoothing time (enco‐
derless)
Speed controller encoderless operation P gain
Speed controller encoderless operation integral time
Acceleration precontrol scaling
≥ 4 · p1452
I
) step-by-step.
P
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Factory setting
1
10 ms
0.3
20 ms
0%
SINAMICS G120X converter

Advertisement

Table of Contents
loading

Table of Contents