Co/Bo: Status Word Speed Controller / Zsw N_Ctrl; Co/Bo: Status Word Current Controller / Zsw I_Ctrl - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

p1402[0...n]
Closed-loop current control and motor model configuration / I_ctrl config
G120X_DP (PM330),
Access level: 4
G120X_PN (PM330),
Can be changed: T, U
G120X_USS (PM330)
Unit group: -
Min:
-
Description:
Sets the configuration for the closed-loop control and the motor model.
Bit field:
Bit
02
Note
For bit 02:
The current controller adaptation (p0391 ... p0393) is only calculated when the bit is set.
r1407.0...23

CO/BO: Status word speed controller / ZSW n_ctrl

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Display and BICO output for the status word of the speed controller.
Bit field:
Bit
00
01
02
03
05
06
07
08
09
10
11
12
13
14
15
17
23
r1408.0...14

CO/BO: Status word current controller / ZSW I_ctrl

Access level: 4
Can be changed: -
Unit group: -
Min:
-
Description:
Display and BICO output for the status word of the current controller.
Bit field:
Bit
00
01
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Signal name
Current controller adaptation active
Signal name
U/f control active
Encoderless operation active
Reserved
Speed control active
Speed controller I component frozen
Speed controller I component set
Torque limit reached
Upper torque limit active
Lower torque limit active
Reserved
Speed setpoint limited
Ramp-function generator set
Encoderless operation due to a fault
I/f control active
Torque limit reached (without precontrol)
Speed limiting control active
Acceleration model activated
Signal name
Current controller active
Id control I component limiting
Calculated: CALC_MOD_REG Data type: Unsigned16
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
-
Yes
Yes
Yes
Yes
Yes
Yes
-
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Active
Active
Parameters
7.2 Parameter list
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
0000 bin
0 signal
FP
No
-
Data type: Unsigned32
Dynamic index: -
Function diagram: 2522
Factory setting:
-
0 signal
FP
No
-
No
-
-
-
No
6040
No
6040
No
6040
No
6060
No
6060
No
6060
-
-
No
6030
No
-
No
-
No
-
No
6060
No
6640
No
-
Data type: Unsigned16
Dynamic index: -
Function diagram: 2530
Factory setting:
-
0 signal
FP
Not active
-
Not active
6714
679

Advertisement

Table of Contents
loading

Table of Contents