Parameters
7.2 Parameter list
Description:
Displays the actual rotor resistance (phase value).
The parameter is affected by the motor temperature model.
Dependency:
See also: p0354, p0620
Note
In each case, only the rotor resistance of the active Motor Data Set is included with the rotor temperature of the thermal
motor model.
This parameter is not used for synchronous motors (p0300 = 2xx).
p0500

Technology application / Tec application

Access level: 2
Can be changed: C2(1), T
Unit group: -
Min:
0
Description:
Sets the technology application.
The parameter influences the calculation of open-loop and closed-loop control parameters that is e.g. initiated using
p0340 = 5.
Value:
0:
1:
2:
3:
5:
Dependency:
For p0096 = 1, 2 (Standard, Dynamic Drive Control) p0500 cannot be changed.
NOTICE
If the technological application is set to p0500 = 0 ... 3 during commissioning (p0010 = 1, 5, 30), the operating mode
(p1300) is pre-set accordingly.
536
Standard drive
Pumps and fans
Sensorless closed-loop control down to f = 0 (passive loads)
Pumps and fans, efficiency optimization
Starting with a high break loose torque
Calculated: -
Scaling: -
Unit selection: -
Max:
5
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0