2.6 Optional components

Procedure, FSA ... FSC

1. Prepare a cutout and holes in the control cabinet panel for the push-through mounting kit.
2. Fix the U-shape frame to the converter using screws (4 × M4 - 2.5 Nm) (step
3. Push the converter heatsink through the cutout of the control cabinet.
4. Fix the converter to the cabinet panel with screws (FSA/FSB: 6 × M6 - 2.5 Nm; FSC: 6 × M6
- 3 Nm) (step
You have correctly installed the converter with the push-through mounting kit.

Procedure, FSD ... FSG

1. Prepare a cutout and holes in the control cabinet panel for the push-through mounting kit.
2. Fix the top and bottom frames (bearing "TOP" and "BOTTOM" marks respectively) to the
converter using screws (FSD/FSE: 8 × M5 - 3 Nm; FSF/FSG: 8 × M8 - 25 Nm) (step
42
Dimension drawings and drill patterns (Page 64)
).
Dimension drawings and drill patterns (Page 64)
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
).
).