Bo: Cu Analog Outputs Status Word / Cu Ao Zsw; Co: Fieldbus Analog Outputs / Fieldbus Ao; Cu Digital Inputs Simulation Mode / Cu Di Simulation - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Parameters
7.2 Parameter list
Index:
[0] = AO0 (X133 12/13)
[1] = AO1 (X202 85/86)
[2] = AO2 (X202 83/84)
Note
AO: Analog Output
X202: IO module terminal
r0785.0...2

BO: CU analog outputs status word / CU AO ZSW

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Displays the status of analog outputs.
Bit field:
Bit
00
01
02
Note
AO: Analog Output
p0791[0...2]

CO: Fieldbus analog outputs / Fieldbus AO

G120X_USS
Access level: 3
Can be changed: T, U
Unit group: -
Min:
-200.000 [%]
Description:
Setting and connector output to control the analog outputs via fieldbus.
Index:
[0] = AO0 (X133 12/13)
[1] = AO1 (X202 85/86)
[2] = AO2 (X202 83/84)
Dependency:
See also: p0771
Note
AO: Analog Output
The following interconnections must be established to control the analog outputs via fieldbus:
- AO 0: p0771[0] with p0791[0]
- AO 1: p0771[1] with p0791[1]
- AO 2: p0771[2] with p0791[2]
X202: IO module terminal
p0795

CU digital inputs simulation mode / CU DI simulation

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the simulation mode for digital inputs.
Bit field:
Bit
576
Signal name
AO 0 negative
AO 1 negative
AO 2 negative
Signal name
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
200.000 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: Unsigned16
Dynamic index: -
Function diagram: 9572
Factory setting:
-
0 signal
FP
No
-
No
-
No
-
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
0.000 [%]
Data type: Unsigned32
Dynamic index: -
Function diagram: 2201, 2221,
2256
Factory setting:
0000 0000 0000 0000 bin
0 signal
FP
SINAMICS G120X converter

Advertisement

Table of Contents
loading

Table of Contents