Motor Saturation Characteristic I_Mag 2 / Mot Sat. I_Mag 2; Motor Saturation Characteristic I_Mag 3 / Mot Sat. I_Mag 3 - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Parameters
7.2 Parameter list
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the x coordinate (magnetizing current) for the 1st value pair of the characteristic.
Sets the first magnetization current of the saturation characteristic in [%] with reference to the rated magnetization
current (r0331).
Dependency:
The following applies for the magnetizing currents:
p0366 < p0367 < p0368 < p0369
See also: p0362
Note
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0367[0...n]

Motor saturation characteristic I_mag 2 / Mot sat. I_mag 2

Access level: 4
Can be changed: T, U
Unit group: -
Min:
5.0 [%]
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the x coordinate (magnetizing current) for the 2nd value pair of the characteristic.
Sets the second magnetization current of the saturation characteristic in [%] with reference to the rated magnetization
current (r0331).
Dependency:
The following applies for the magnetizing currents:
p0366 < p0367 < p0368 < p0369
See also: p0363
Note
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0368[0...n]

Motor saturation characteristic I_mag 3 / Mot sat. I_mag 3

Access level: 4
Can be changed: T, U
Unit group: -
Min:
5.0 [%]
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the x coordinate (magnetizing current) for the 3rd value pair of the characteristic.
Sets the third magnetization current of the saturation characteristic in [%] with reference to the rated magnetization
current (r0331).
Dependency:
The following applies for the magnetizing currents:
p0366 < p0367 < p0368 < p0369
See also: p0364
Note
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
532
Calculated: -
Scaling: -
Unit selection: -
Max:
800.0 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
800.0 [%]
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: FloatingPoint32
Dynamic index: MDS, p0130
Function diagram: 6723, 6838
Factory setting:
75.0 [%]
Data type: FloatingPoint32
Dynamic index: MDS, p0130
Function diagram: 6723, 6838
Factory setting:
150.0 [%]