r0087

CO: Actual power factor / Cos phi act

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Displays the actual active power factor.
This value refers to the electrical power of the basic fundamental signals at the output terminals of the converter.
r0089[0...2]

Actual phase voltage / U_phase act val

Access level: 4
Can be changed: -
Unit group: 5_3
Min:
- [V]
Description:
Displays the actual phase voltage.
Index:
[0] = Phase U
[1] = Phase V
[2] = Phase W
Note
The values are determined from the transistor switch-on duration.
p0096

Application class / Appl_class

Access level: 1
Can be changed: C2(1)
Unit group: -
Min:
0
Description:
Setting the commissioning and control view for various application classes.
Value:
0:
1:
2:
Dependency:
The parameter is preset when commissioning the system for the first time and for the factory setting, depending on the
power unit that is connected (Power unit is more than 18KW, p0096=2. Power unit is less than 18KW, p0096=1).
Depending on the setting, the ability to see control parameters is restricted depending on the particular application.
The following applies for p0096 > 0:
The motor data identification routine is preset (p1900 = 2).
The following applies for p0096 = 1:
The motor type (p0300) synchronous or reluctance motor is not possible.
Note
When changing p0096 to 1 or 2, when completing commissioning, fast parameterization should be executed (p3900
> 0).
Depending on the setting, after quick commissioning and/or automatic parameterization, the procedure for motor data
identification as well as the setting of the operating mode and parameterization of the closed-loop control must be
appropriately adapted.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Expert
Standard Drive Control (SDC)
Dynamic Drive Control (DDC)
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: p2001
Unit selection: p0505
Max:
- [V]
Calculated: -
Scaling: -
Unit selection: -
Max:
2
Parameters
7.2 Parameter list
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
-
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6730
Factory setting:
- [V]
Data type: Integer16
Dynamic index: -
Function diagram: 6019
Factory setting:
0