Siemens SINAMICS G120X Operating Instructions Manual page 641

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Description:
Sets the signal source for the command "continue ramp-function generator/freeze ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 5 (STW1.5).
BI: p1141 = 0 signal:
Freezes the ramp-function generator.
BI: p1141 = 1 signal:
Continue ramp-function generator.
Dependency:
See also: r0054, p1140, p1142
CAUTION
When "master control from PC" is activated, this binector input is ineffective.
NOTICE
The ramp-function generator is, independent of the state of the signal source, active in the following cases:
- OFF1/OFF3.
- ramp-function generator output within the suppression bandwidth.
- ramp-function generator output below the minimum speed.
p1141[0...n]
BI: Continue ramp-function generator/freeze ramp-function generator / Continue RFG
G120X_USS
Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source for the command "continue ramp-function generator/freeze ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 5 (STW1.5).
BI: p1141 = 0 signal:
Freezes the ramp-function generator.
BI: p1141 = 1 signal:
Continue ramp-function generator.
Dependency:
See also: r0054, p1140, p1142
CAUTION
When "master control from PC" is activated, this binector input is ineffective.
NOTICE
The ramp-function generator is, independent of the state of the signal source, active in the following cases:
- OFF1/OFF3.
- ramp-function generator output within the suppression bandwidth.
- ramp-function generator output below the minimum speed.
p1142[0...n]
BI: Enable setpoint/inhibit setpoint / Setpoint enable
G120X_DP,
Access level: 3
G120X_PN
Can be changed: T
Unit group: -
Min:
-
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Parameters
7.2 Parameter list
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2501
Factory setting:
1
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2501
Factory setting:
[0] 2090.6
[1] 1
[2] 2090.6
[3] 2090.6
639