Magnetization Rate Time Scaling / Mag Tv Scale; Co: Synchronous Reluctance Motor Flux Channel / Resm Flux Channel - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Description:
The following applies for a synchronous reluctance motor:
Displays the transition value for the start of the evaluation of the optimum flux characteristic.
The value is referred to the rated motor torque.
Note
The transition value corresponds with the lower limit of the flux setpoint (p1581).
For a lower absolute torque setpoint, the flux setpoint remains at the lower limit (p1581).
p1567[0...n]

Magnetization rate time scaling / Mag Tv scale

Access level: 4
Can be changed: T, U
Unit group: -
Min:
0 [%]
Description:
The following applies for a synchronous reluctance motor:
Sets the scaling of the rate time Tv for dynamic flux increase when the torque is quickly established.
The value is referred to the inverse value of the rated motor frequency.
Tv = p1567 / 100 % / p0310
Dependency:
See also: p1401
Note
The "Dynamic load-dependent flux boost" function can be deactivated using p1401.9 = 0.
r1568[0...5]

CO: Synchronous reluctance motor flux channel / RESM flux channel

Access level: 4
Can be changed: -
Unit group: -
Min:
- [%]
Description:
Display and connector output for signals of the flux channel for a synchronous reluctance motor (RESM).
The values are referred to the rated motor flux of the in-line axis (p0357 * r0331).
Index:
[0] = Setpoint before filter
[1] = Optimum flux characteristic output
[2] = Minimum value at low speed
[3] = Dynamic load-dependent boost
[4] = Field weakening value total
[5] = Field weakening value precontrol
Note
RESM: reluctance synchronous motor (synchronous reluctance motor)
p1570[0...n]
CO: Flux setpoint / Flex setp
Access level: 3
Can be changed: T, U
Unit group: -
Min:
50.0 [%]
Description:
Sets the flux setpoint referred to rated motor flux.
The following applies for a synchronous reluctance motor:
Scaling the flux setpoint.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Calculated: CALC_MOD_CON Data type: FloatingPoint32
Scaling: -
Unit selection: -
Max:
1000 [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
- [%]
Calculated:
CALC_MOD_LIM_REF
Scaling: PERCENT
Unit selection: -
Max:
200.0 [%]
Parameters
7.2 Parameter list
Dynamic index: DDS, p0180
Function diagram: 6790
Factory setting:
100 [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
- [%]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 6722
Factory setting:
100.0 [%]
691