Trace: Recording Not Possible As A Result Of Know-How Protection; Trace: Recording Time Too Short; Trace: Recording Cycle Too Short; Trace: Time Slice Clock Cycle Invalid - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Cause:
The trace has already been started.
See also: p4700 (Trace control)
Remedy:
Stop the trace and, if necessary, start again.
A02051

Trace: recording not possible as a result of know-how protection

Reaction:
NONE
Acknowledge:
NONE
Cause:
TRACE recording is not possible as at least one signal or trigger signal being used is under know-how protection.
Alarm value (r2124, interpret decimal):
1: Recorder 0
2: Recorder 1
3: Recorders 0 and 1
See also: p4700, p4711, p4730, p4731, p4732, p4733, p4734, p4735, p4736, p4737
Remedy:
- Temporarily activate or deactivate know-how protection (p7766).
- include the signal in the OEM exception list (p7763, p7764).
- Where relevant do not record the signal.
See also: p7763, p7764
A02055

Trace: Recording time too short

Reaction:
NONE
Acknowledge:
NONE
Cause:
The trace duration is too short.
The minimum is twice the value of the trace clock cycle.
See also: p4721 (Trace recording time)
Remedy:
Check the selected recording time and, if necessary, adjust.
A02056

Trace: Recording cycle too short

Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected recording clock cycle is lower than the basic clock cycle 500µs.
See also: p4720 (Trace recording cycle)
Remedy:
Increase the value for the trace cycle.
A02057

Trace: Time slice clock cycle invalid

Reaction:
NONE
Acknowledge:
NONE
Cause:
The time slice clock cycle selected does not match any of the existing time slices.
See also: p4723 (Trace time slice cycle)
Remedy:
Enter an existing time slice clock cycle. The existing time slices can be read out via p7901.
See also: r7901 (Sampling times)
A02058
Trace: Time slice clock cycle for endless trace not valid
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected time slice clock cycle cannot be used for the endless trace
See also: p4723 (Trace time slice cycle)
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Warnings, faults and system messages
9.6 List of fault codes and alarm codes
989