p29611[0...n]

Pipe filling mode / PF mode

Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Selects the mode for pipe filling.
Value:
0:
1:
p29612[0...n]

Pipe filling speed / PF spd

Access level: 3
Can be changed: T
Unit group: 3_1
Min:
-210000.00 [rpm]
Description:
Sets the speed applied to the motor for the pipe filling.
p29613[0...n]

Pipe filling time / PF time

Access level: 3
Can be changed: T
Unit group: -
Min:
0.50 [s]
Description:
Sets the duration time for the pipe filling.
p29614[0...n]

Pipe filling threshold / PF thresh

Access level: 3
Can be changed: T
Unit group: 9_1
Min:
0.00 [%]
Description:
Defines the threshold for stopping the pipe filling. The filling stops if the actual PID feedback reaches the threshold.
It's used when p29611=1.
p29615[0...n]
Pipe filling monitoring time / PF mon time
Access level: 3
Can be changed: T
Unit group: -
Min:
0.00 [s]
Description:
Monitors the duration time for actual pressure (r2272) >= the threshold (p29614). The pipe filling stops if the duration
time is reached.
Note
It is used when p29611 = 1.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
The pipe is filled based on specified time
The pipe is filled based on the actual pressure feedback
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Calculated: -
Scaling: p2000
Unit selection: p0505
Max:
210000.00 [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max:
10000.00 [s]
Calculated: -
Scaling: -
Unit selection: p0595
Max:
100.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
100.00 [s]
Parameters
7.2 Parameter list
Data type: Integer16
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
0
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
900.00 [rpm]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
50.00 [s]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
10.00 [%]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
0.00 [s]