Message For A Memory Card That Is Not Inserted; Activate Message; Deactivate Message - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

8.1.5

Message for a memory card that is not inserted

Function description
The converter identifies that a memory card is not inserted, and signals this state. The message
is deactivated in the converter factory setting.

Activate message

Procedure
1. Set p2118[x] = 1101, x = 0, 1, ... 19
2. Set p2119[x] = 2
Message A01101 for a memory card that is not inserted is activated.
To cyclically signal to the higher-level control that a memory card is not inserted, connect
parameter r9401 to the send data of the fieldbus interface.

Deactivate message

Procedure
1. Set p2118[x] = 1101, x = 0, 1, ... 19
2. Set p2119[x] = 3
Message A01101 for a memory card that is not inserted is deactivated.
Parameter
Parameter
p2118[0 ... 19]
p2119[0 ... 19]
r9401
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Explanation
Change message type, message number
Change message type, type
Safely remove memory card status
Saving the settings and series commissioning
Factory setting
0
0
-
8.1 Memory card
945