Requirements for line reactors

Rated power of converter (kW)
315 ... 500
> 500
It is recommended that a line reactor is always connected on the line side of the converter, as
in practice, it is often not known on which supply configuration individual converters are to be
operated, i.e. which supply short-circuit power is present at the converter connection point.
A line reactor can only be dispensed with when the value for R
table. This is the case, when the converter, as shown in the following figure, is connected to the
line through a transformer with the appropriate rating.
Note
A line reactor is always needed if a line filter is used.
In this case, the line short-circuit power S
approximately:
S
k1
S
transf
S
k2 line
U
k transf
34
Line reactor can be omitted for
R
SC
≤ 33
≤ 20
= S
/ (U
+ S
transf
k transf
transf
= Transformer rated power
= Short-circuit power of the higher-level voltage level
= Relative short-circuit voltage
at the connection point of the converter is
k1
/ S
)
k2 line
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Line reactor is required for R
> 33
> 20