Description:
Sets the tolerance time for line phase monitoring for blocksize power units.
If a line phase fault is present for longer than this tolerance time, then a corresponding fault is output.
Dependency:
See also: F30011
NOTICE
When operating with a failed line phase, depending on the active power, values higher than the default value can either
immediately damage the power unit or damage it over the long term.
Note
For the setting p1822 = maximum value, line phase monitoring is deactivated.
p1825

Converter valve threshold voltage / Threshold voltage

Access level: 4
Can be changed: T, U
Unit group: -
Min:
0.0 [Vrms]
Description:
Sets the threshold voltage drop of the valves (power semiconductor devices) to be compensated.
Note
The value is automatically calculated in the motor data identification routine.
p1828

Compensation valve lockout time phase U / Comp t_lock ph U

Access level: 4
Can be changed: T, U
Unit group: -
Min:
0.00 [µs]
Description:
Sets the valve lockout time to compensate for phase U.
Note
The value is automatically calculated in the motor data identification routine.
p1828
Compensation valve lockout time phase U / Comp t_lock ph U
G120X_DP (PM330),
Access level: 4
G120X_PN (PM330),
Can be changed: T, U
G120X_USS (PM330)
Unit group: -
Min:
0.00 [µs]
Description:
Sets the valve lockout time to compensate for phase U.
Note
The value is automatically calculated in the motor data identification routine.
p1829

Compensation valve lockout time phase V / Comp t_lock ph V

Access level: 4
Can be changed: T, U
Unit group: -
Min:
0.00 [µs]
Description:
Sets the valve lockout time to compensate for phase V.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Scaling: -
Unit selection: -
Max:
100.0 [Vrms]
Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Scaling: -
Unit selection: -
Max:
3.99 [µs]
Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Scaling: -
Unit selection: -
Max:
7.80 [µs]
Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Scaling: -
Unit selection: -
Max:
3.99 [µs]
Parameters
7.2 Parameter list
Dynamic index: -
Function diagram: -
Factory setting:
0.6 [Vrms]
Dynamic index: -
Function diagram: -
Factory setting:
0.00 [µs]
Dynamic index: -
Function diagram: -
Factory setting:
0.00 [µs]
Dynamic index: -
Function diagram: -
Factory setting:
0.00 [µs]
715