Parameters
7.2 Parameter list
p1901
Test pulse evaluation configuration / Test puls config
G120X_DP (PM330),
Access level: 3
G120X_PN (PM330),
Can be changed: T
G120X_USS (PM330)
Unit group: -
Min:
-
Description:
Sets the configuration for the test pulse evaluation.
Bit 00: Check for conductor-to-conductor short circuit once/always when the pulses are enabled.
Bit 01: Check for ground fault once/always when the pulses are enabled.
Bit 02: Activation of the tests selected using bit 00 and/or bit 01 each time the pulses are enabled
Recommendation:
If the ground fault test is incorrectly initiated because the motor is not at a complete standstill, then the pulse
cancellation delay time (p1228) should be increased.
Bit field:
Bit
00
01
02
Dependency:
The ground fault test is only possible when the motor is stationary, and is therefore only realized when flying restart
is deactivated (p1200 = 0).
See also: p0287
Note
If a conductor-to-conductor short-circuit is detected during the test, this is displayed in r1902.1.
If a ground fault is detected during the test, this is displayed in r1902.2.
For bit 02 = 0:
If the test was successful once after POWER ON (see r1902.0), then it is not repeated.
For bit 02 = 1:
The test is not only performed after POWER ON, but also each time the pulses are enabled.
For chassis power units, the ground fault is also determined using the summed output current (see p0287).
r1902

Test pulse evaluation status / Test puls ev stat

Access level: 4
Can be changed: -
Unit group: -
Min:
-
Description:
Displays the status of the test pulse evaluation.
Bit field:
Bit
00
01
02
03
04
05
06
07
08
Note
If the ground fault test was selected, but not successfully performed, then sufficient current was not be able to be
established during the test pulses.
For bit 04:
A test pulse longer than one sampling time has occurred
720
Signal name
Phase short-circuit test pulse active
Ground fault detection test pulse active
Test pulse at each pulse enable
Signal name
Short-circuit test successfully performed
Phase short-circuit detected
Ground fault test successfully performed
Ground fault detected
Identification pulse width greater than the minimum pulse
width
Pulse frequency for short-circuit test requested
Short-circuit test in power stack driver activated
Short-circuit test pulse suppression active
Motor phase interrupted
Calculated: CALC_MOD_ALL Data type: Unsigned32
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Dynamic index: -
Function diagram: -
Factory setting:
0000 bin
0 signal
FP
No
-
No
-
No
-
Data type: Unsigned32
Dynamic index: -
Function diagram: -
Factory setting:
-
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
SINAMICS G120X converter

Advertisement

Table of Contents
loading

Table of Contents