Changing settings using BOP-2

Changing settings using BOP-2
You can modify the settings of your converter by changing the values of the its parameters. The
converter only permits changes to "write" parameters. Write parameters begin with a "P", e.g.
P45.
The value of a read-only parameter cannot be changed. Read-only parameters begin with an
"r", for example: r2.
The converter retentively saves all the changes made using the BOP-2 so that they are
protected against power failure.
Procedure
1. Select the menu to display and change parameters.
Press the OK key.
2. Select the parameter filter using the arrow keys.
Press the OK key.
– STANDARD: The converter only displays the most important parameters.
– EXPERT: The converter displays all of the parameters.
3. Select the required number of a write parameter using the arrow keys.
Press the OK key.
4. Select the value of the write parameter using the arrow keys.
Accept the value with the OK key.
You have now changed a write parameter using the BOP-2.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
5.6 Handling the BOP-2 operator panel
Commissioning
175