6.3.4.4

The converter as Ethernet node

Integrating a converter into an Ethernet network (assigning an IP address)
Procedure
1. Set p8924 (PN DHCP mode) = 2 or 3
– p8924 = 2: The DHCP server assigns the IP address based on the MAC address of the
– p8924 = 3: The DHCP server assigns the IP address based on the device name of the
2. Save the settings with p8925 = 2. The next time that the converter switches on, it retrieves
the IP address, and you can address the converter as Ethernet node.
Note
Immediate switchover without restart
The switchover to DHCP is performed immediately and without a restart if the change is
carried out with the EtherNet/IP command "Set Attribute Single" (class F5 hex, attribute 3).
The following options are available:
● via an EtherNet/IP controller
● via an EtherNet/IP commissioning tool
You have now integrated the converter into Ethernet
Displays
r8930: Device name of the converter
r8934: Operating mode, PN or DHCP
r8935: MAC address
Additional information
You can find information about parameters and messages (A08565) in the parameter list.

Additional options of integrating converters into Ethernet

You also have the option of integrating the converter into Ethernet using Proneta or STEP 7, for
example.
Here is the example of the "Edit Ethernet station" screen form from Step 7, which you can use
to make the required settings.
SINAMICS G120X converter