p0626[0...n]

Motor overtemperature, stator core / Mot T_over core

Access level: 4
Can be changed: T, U
Unit group: 21_2
Min:
10 [K]
Description:
Defines the rated overtemperature of the stator iron referred to ambient temperature in the motor temperature model
2 (p0612.1 = 1).
Dependency:
For 1LA7 motors (p0300), the parameter is pre-set as a function of p0307 and p0311.
See also: p0625
NOTICE
When selecting a standard induction motor listed in the catalog (p0300 > 100, p0301 > 10000), this parameter is
automatically pre-assigned and is write protected. Information in p0300 should be carefully observed when removing
write protection.
Note
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0627[0...n]

Motor overtemperature, stator winding / Mot T_over stator

Access level: 2
Can be changed: T, U
Unit group: 21_2
Min:
15 [K]
Description:
Defines the rated overtemperature of the stator winding referred to the ambient temperature.
- motor temperature model 1 (I2t, p0612.0 = 1):
The following applies for firmware version < 4.7 SP6 or p0612.8 = 0:
p0605 is of significance for the rated temperature.
The following applies from firmware version 4.7 SP6 and p0612.8 = 1:
Overtemperature at the rated operating point.
- motor temperature model 2 (p0612.1 = 1):
Overtemperature at the rated operating point.
Dependency:
For 1LA5 and 1LA7 motors (p0300 = 15, 17), the parameter is pre-set as a function of p0307 and p0311.
See also: p0625
NOTICE
When selecting a standard induction motor listed in the catalog (p0300 > 100, p0301 > 10000), this parameter is
automatically pre-assigned and is write protected. Information in p0300 should be carefully observed when removing
write protection.
Note
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
The signal is not suitable as a process quantity and may only be used as a display quantity.
p0628[0...n]

Motor overtemperature rotor / Mot T_over rotor

Access level: 4
Can be changed: T, U
Unit group: 21_2
Min:
20 [K]
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Calculated: CALC_MOD_EQU Data type: FloatingPoint32
Scaling: -
Unit selection: p0505
Max:
200 [K]
Calculated: CALC_MOD_EQU Data type: FloatingPoint32
Scaling: -
Unit selection: p0505
Max:
200 [K]
Calculated: CALC_MOD_EQU Data type: FloatingPoint32
Scaling: -
Unit selection: p0505
Max:
200 [K]
Parameters
7.2 Parameter list
Dynamic index: MDS, p0130
Function diagram: 8018
Factory setting:
50 [K]
Dynamic index: MDS, p0130
Function diagram: 8017, 8018
Factory setting:
80 [K]
Dynamic index: MDS, p0130
Function diagram: 8018
Factory setting:
100 [K]